7-2. Operation Data
<Cooling>
Model name Standard Indoor Outdoor Compressor
pressure fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
27/19 35/- 42NQV025M 0.9 to 1.1 9 to 11 47 to 49 High High 54
42NQV025M-A
0.9 to 1.1 9 to 11 47 to 49 High High 54
condition(°C)
Tempeature Heat exchanger
pipe temp.
Model name Standard Indoor Outdoor Compressor
pressure fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
20/- 7/6 42NQV025M 2.4 to 2.6 43 to 45 0 to 3 High High 68
42NQV025M-A 2.4 to 2.6 43 to 45 0 to 3 High High 68
Tempeature Heat exchanger
condition(°C) pipe temp.
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 m
<Heating>
FILE NO. SVM-07009