8.2.3 15C 
 
 
 
8.3 Main Protection 
8.3.1 Three minutes delay at restart for compressor. 
8.3.2 Sensor protection at open circuit and breaking disconnection. 
8.3.3 Indoor fan delayed open function   
----When system starts up, the louver will be active immediately, and the indoor fan will open after certain 
time. 
----If the system runs in heating mode, the anti-cold wind function has priority. 
8.3.4 Fan speed is out of control (For the units used DC fan motor) 
For console: 
When indoor fan speed keeps too low (300RPM) for certain time, the unit will stop and the LED will display 
the failure.   
For other models: 
When indoor fan speed keeps too low (lower than 300 RPM) for 50s, the indoor fan will shut off and restart 
30s later, if protection happened 3 times when fan motor restart continuously, the unit will stop and the LED 
will display the failure. 
8.3.5 Inverter module protection 
The Inverter module has a protection function about current, voltage and temperature. If these protections 
happen, the corresponding code will display on indoor unit and the unit will stop working. 
 