1)  If the indoor PCB receives the signal which results from pressing the FOLLOW ME button on remote 
controller, the buzzer will emit a sound and this indicates the follow me function is initiated. But when the 
indoor PCB receives signal  which  sent from remote controller every 3  minutes, the buzzer will  not 
respond. When the unit is running with follow-me function, the PCB will control the unit according to the 
temperature from follow-me signal, and the temperature collection function of room temperature sensor 
will be shielded, and the error detective function of room temperature sensor will be still invalid. 
2)  When the follow-me function is available, the PCB will not respond according to the setting temperature 
from follow-me signal every 3 minutes. 
3)  The  PCB  will  take  action  to  the  mode  change  information  from  remote  controller  signal,  and  the 
follow-me function will be turned off. (if the wired remote controller does not initiate follow me function). 
4)  When the unit is running with follow-me function, if  the PCB doesn’t receive any signal  from remote 
controller for 7 minutes or pressing FOLLOW ME button again, the follow-me function will be turned off 
automatically, and the temperature collection function of room temperature sensor will be available, the 
PCB will control the unit according to the room temperature detected from its own room temperature 
sensor and setting temperature. 
5)  When the indoor PCB receives the follow-me signal from wired remote controller, the control is the 
same as that from wireless remote controller, but buzzer will not emit a sound. When the PCB receives 
turning-off follow-me signal from wired remote controller, the unit will quit follow-me function at once. 
The follow-me function controlled by wired remote controller prevails that by wireless remote controller.   
 
8.4.12 Mode conflict 
The indoor units can not work cooling mode and heating at same time.   
Heating mode has a priority. 
(1) Definition   
No: No mode conflict; 
Yes: Mode conflict 
(2) Unit action 
  In case of one Indoor unit working in cooling mode or fan mode, and another indoor unit is set to heating 
mode, the indoor unit working in cooling mode or fan mode will change to off. The outdoor unit will 
change to heating mode after compressor stop 3 minutes. . 
  In case of one Indoor unit working in heating mode, and another indoor unit is set to cooling mode or fan 
mode, the indoor unit setting to cooling mode or fan mode will change to stand by. The outdoor unit will 
continue working in heating mode. 
If heating mode stops (not including the indoor unit in heating mode reaching the set temperature), 3 
minutes after the outdoor unit restarts and works in cooling mode or fan-only mode.