A
B
A
B
Terminal block for remote
controller wiring of indoor unit
Terminal block
Remote
controller unit
Remote controller
wire (Procured locally)
11-3. Remote Controller Wiring
s Strip off approx. 9 mm the wire to be connected.
s For single system, use non polarity, 2 core wire is
used for wiring of the remote
controller.(0.5 mm² to 2.0 mm² wires)
s For the synchronous twin, triple system, use
2-conre shield wire (Vinyl cord for microphone 0.5
to 2.0 mm²) to conform to the EMC standard.
∗ For details of wiring/installation of the remote
controller, refer to the Installation Manual enclosed
with the remote controller.
Wiring diagram
A B
1
1
L N
2
2
3
3
Power supply
Single system
Remote controller
Remote controller wiring
Indoor side
Indoor/Outdoor
connecting wires
Outdoor side
A B
1
1
L N
2
2
3
3
Power supply
Simultaneous twin system
Remote controller
Remote controller wiring
Indoor side
Indoor/Outdoor
connecting wires
Outdoor side
(Example of 2-lines cabling)
(Real line: Cabling, Broken line: Refrigerant pipe)
For the above example, perform setting by
connecting singly the wired remote controller
without remote controller inter-unit cable.
Individual : 0000
Master unit : 0001
Sub unit : 0002
Indoor
A B
A B
1 2 3
Indoor
A B
1 2 3
Indoor
A B
1 2 3
Indoor
A B
1 2 3
1 23
Outdoor Outdoor
1 2 3
Remote controller
Line address o 1
Indoor unit address o 1
Group address o 1
1
2
2
2
1
2
2
2
2
11-4. Address Setup (Manual setting from remote controller)
In case that addresses of the indoor units will be
determined prior to piping work after cabling work
s Set an indoor unit per a remote controller.
s Turn on power supply.
SVM-13072.indb 89SVM-13072.indb 89 11/01/13 1:53 PM11/01/13 1:53 PM
Group address
In case of group control