Step 3 - Anchor the Outdoor Unit
• The outdoor unit can be anchored to the ground or to a wall-mounted bracket with bolt (M10). Prepare the installation base of the unit according to
Figure 13.
Fig. 13 — Anchor the Outdoor unit
When Selecting the 45MBAA 24K/30K/33K/36K
Indoor Unit
A single 24K/30K/33K/36K indoor unit must be connected to the
“A” circuit. If there are two 24K/30K/33K/36K indoor units, they
must be connected with A and B circuits.
Fig. 14 — A and B Circuits
NOTE: (A,B,C,D,E circuits) If the Air Handler (45MBAA) is
selected as one of the indoor units to be connected to the
multi-zone outdoor unit, larger ports should be used with
ports that have a 1/2 inch suction pipe diameter.
If you install the unit on a wall-mounted bracket, perform the
following steps.
1. Mark the position of bracket holes based on the dimensions chart.
2. Pre-drill the holes for the expansion bolts.
3. Place a washer and nut on the end of each expansion bolt.
4. Thread expansion bolts through holes in the mounting brackets, put
mounting brackets in position, and hammer the expansion bolts into the
wall.
5. Ensure the mounting brackets are level.
6. Carefully lift unit and place its mounting feet on brackets.
7. Bolt the unit firmly to the brackets.
8. If allowed, install the unit with rubber gaskets to reduce vibrations and
noise.
When drilling into concrete, eye protection is recommended at all
times.
WA R N I N G
W
H
W
H
Front view
Outdoor Unit Types and
Specifications
(Split Type Outdoor Unit)
Ensure the wall is made of solid brick, concrete, or of similarly
strong material. The wall must be able to support at least four times
the weight of the unit.
CAUTION