CL-3
ITEM EXPANSION RANGE DEFAULT ENTRY
BP BUILDING PRESS. CONFIG
→
BP.CF Building Press. Config 0-2 0
→
BP.MT Power Exhaust Motors 1-2 1
→
BP.S Building Pressure Sensor Enable/Dsable Dsable
→
BP.R Bldg Press (+/-) Range 0 - 1.00 0.25
→
BP.SP Building Pressure Setp. –0.25 
→
 0.25 "H2O 0.05
→
BP.P1 Power Exhaust On Setp.1 0 - 100 % 35
→
BP.P2 Power Exhaust On Setp.2 0 - 100 % 75
→
B.CFG BP ALGORITHM CONFIGS
→
B.CFG
→
BP.SL Modulating PE Alg. Slct. 1-3 1
→
B.CFG
→
BP.TM BP PID Evaluation Time 0 - 10 min 1
→
B.CFG
→
BP.ZG BP Threshold Adjustment 0.1 - 10.0 1
→
B.CFG
→
BP.HP High BP Level 0 - 1.000 0.05
→
B.CFG
→
BP.LP Low BP Level 0 - 1.000 0.04
D.LV.T COOL/HEAT SETPT. OFFSETS
→
L.H.ON Dmd Level    Lo Heat On –1 - 2 ^F 1.5
→
H.H.ON Dmd Level(+) Hi Heat On 0.5 - 20.0 ^F 0.5
→
L.H.OF Dmd Level(-) Lo Heat Off 0.5 - 2 ^F 1
→
L.C.ON Dmd Level    Lo Cool On –1 - 2 ^F 1.5
→
H.C.ON Dmd Level(+) Hi Cool On 0.5 - 20.0 ^F 0.5
→
L.C.OF Dmd Level(-) Lo Cool Off 0.5 - 2 ^F 1
→
C.T.LV Cool Trend Demand Level 0.1 - 5 ^F 0.1
→
H.T.LV Heat Trend Demand Level 0.1 - 5 ^F 0.1
→
C.T.TM Cool Trend Time 30 - 600 sec 120
→
H.T.TM Heat Trend Time 30 - 600 sec 120
DMD.L DEMAND LIMIT CONFIG.
→
DM.L.S Demand Limit Select 0 - 3 (multi-text strings) 0
→
D.L.20 Demand Limit at 20 ma 0 - 100 % 100
→
SH.NM Loadshed Group Number 0 - 99 0
→
SH.DL Loadshed Demand Delta 0 - 60 % 0
→
SH.TM Maximum Loadshed Time 0 - 120 min 60
→
D.L.S1 Demand Limit Sw.1 Setpt. 0 - 100 % 80
→
D.L.S2 Demand Limit Sw.2 Setpt. 0 - 100 % 50
IAQ INDOOR AIR QUALITY CFG.
→
DCV.C DCV ECONOMIZER SETPOINTS
→
DCV.C
→
EC.MN Economizer Min.Position 0 - 100 % 5
→
DCV.C
→
IAQ.M IAQ Demand Vent Min.Pos. 0 - 100 % 0
→
AQ.CF AIR QUALITY CONFIGS
→
AQ.CF
→
IQ.A.C IAQ Analog Sensor Config 0 - 4 (multi-text strings) 0
→
AQ.CF
→
IQ.A.F IAQ 4-20 ma Fan Config 0 - 2 (multi-text strings) 0
→
AQ.CF
→
IQ.I.C IAQ Discrete Input Config 0 - 2 (multi-text strings) 0
→
AQ.CF
→
IQ.I.F IAQ Disc.In. Fan Config 0 - 2 (multi-text strings) 0
→
AQ.CF
→
OQ.A.C OAQ 4-20ma Sensor Config 0 - 2 (multi-text strings) 0
→
AQ.SP AIR QUALITY SETPOINTS
→
AQ.SP
→
IQ.O.P IAQ Econ Override Pos. 0 - 100 % 100
→
AQ.SP
→
DAQ.L Diff.Air Quality LoLimit 0 - 1000 100
→
AQ.SP
→
DAQ.H Diff.Air Quality HiLimit 100 - 2000 700
→
AQ.SP
→
D.F.OF DAQ PPM Fan Off Setpoint 0 - 2000 200
→
AQ.SP
→
D.F.ON DAQ PPM Fan On Setpoint 0 - 2000 400
→
AQ.SP
→
IAQ.R Diff. AQ Responsiveness –5 - 5 0
→
AQ.SP
→
OAQ.L OAQ Lockout Value 0 - 2000 0
→
AQ.SP
→
OAQ.U User Determined OAQ 0 - 5000 400
→
AQ.S.R AIR QUALITY SENSOR RANGE
→
AQ.S.R
→
IQ.R.L IAQ Low Reference 0 - 5000 0
→
AQ.S.R
→
IQ.R.H IAQ High Reference 0 - 5000 2000
→
AQ.S.R
→
OQ.R.L OAQ Low Reference 0 - 5000 0
→
AQ.S.R
→
OQ.R.H OAQ High Reference 0 - 5000 2000
→
IAQ.P IAQ PRE-OCCUPIED PURGE
→
IAQ.P
→
IQ.PG IAQ Purge Yes/No No
→
IAQ.P
→
IQ.P.T IAQ Purge Duration 5-60 min 15
→
IAQ.P
→
IQ.P.L IAQ Purge LoTemp Min Pos 0-100 % 10
→
IAQ.P
→
IQ.P.H IAQ Purge HiTemp Min Pos 0-100 % 35
→
IAQ.P
→
IQ.L.O IAQ Purge OAT Lockout 35-70 dF 50