123
APPENDIX E: BACnet Points List
Analog Value (AV) Points (cont)
POINT DESCRIPTION POINT ACCESS UNITS
BACnet OBJECT
NAME
BACnet ID VALUE RANGE
CCN POINT
EQUIVALENT
Occ Heating required READ ONLY °F lnk_ohrq AV:265 0TO30 LNK_OHRQ
Occupied Cool Setpoint R/W °F ocsp AV:288 55 TO 80 OCSP
Occupied Heat Setpoint R/W °F ohsp AV:289 55 TO 80 OHSP
Occupied Setpoint Gap R/W odb AV:6003 0TO10 ODB
Occupied SPRH Setpoint READ ONLY % sprh_osp AV:367 0.10 TO 1 SPRH_OSP
Occupied Zone Setpoint R/W °F osp AV:6002 40 TO 80 OSP
ODF High Speed Time R/W sec minodftm AV:280 0 TO 300 MINODFTM
ODF Relay Resets Counts READ ONLY rs_ofr AV:8044 0 TO 65535 RS_OFR
ODF Relay Run Hours READ ONLY hrs hour_ofr AV:8043 0 TO 999999 HR_OFR
ODF Relay Starts READ ONLY st_ofr AV:8045 0 TO 999999 ST_OFR
Outdoor Air Enthalpy R/W BTU_LB oa_enth AV:76 --- 9.6f TO 334.2f OA_ENTH
outdoor Air in CFM R/W CFM oacfm AV:416 0 TO 5000 OACFM
Outdoor Air Temp Sensor READ ONLY °F oat_loc AV:286 --- 40 TO 245 OAT_LOC
Outdoor Air Temperature R/W °F oa_temp AV:1003 --- 40 TO 245 OAT
P.Exhaust 1 Curve Offset READ ONLY % pe1_offs AV:317 0TO1 PE1_OFFS
P.Exhaust 1 Resets Count READ ONLY rs_pe_1 AV:113 0 TO 65535 RS_PE_1
P.Exhaust 2 Curve Offset READ ONLY % pe2_offs AV:229 0TO1 PE2_OFFS
P.Exhaust 2 Resets Count READ ONLY rs_pe_2 AV:114 0 TO 65535 RS_PE_2
PE Stage 1 At Max Speed R/W % pe1_pmax AV:343 0TO1 PE1_PMAX
PE Stage 2 At Max Speed R/W % pe2_pmax AV:344 0TO1 PE2_PMAX
PE Turn Off Dead band R/W % pe_offdb AV:316 0TO1 PE_OFFDB
PE1 Assigned Relay R/W pe1_channel AV:365 0TO2 PE1_CHAN
PE2 Assigned Relay R/W pe2_channel AV:366 0TO2 PE2_CHAN
Pilot Space Temp Value R/W °F space_temp AV:2007 --- 40 TO 245 SPT
Power Cycle Counts READ ONLY st_por AV:150 0 TO 999999 ST_POR
Power Cycle Resets Count READ ONLY rs_por AV:115 0 TO 65535 RS_POR
Power Exhaust 1 --- Pos 1 READ ONLY % pe1_pos1 AV:345 0TO1 PE1_POS1
Power Exhaust 1 --- Pos 2 READ ONLY % pe1_pos2 AV:346 0TO1 PE1_POS2
Power Exhaust 1 --- Pos 3 READ ONLY % pe1_pos3 AV:347 0TO1 PE1_POS3
P o w e r E x h a u s t 1 --- S p e e d 1 READ ONLY % pe1_spd1 AV:348 0TO1 PE1_SPD1
P o w e r E x h a u s t 1 --- S p e e d 2 READ ONLY % pe1_spd2 AV:349 0TO1 PE1_SPD2
P o w e r E x h a u s t 1 --- S p e e d 3 READ ONLY % pe1_spd3 AV:350 0TO1 PE1_SPD3
Power Exhaust 1 Starts READ ONLY st_pe_1 AV:148 0 TO 999999 ST_PE_1
Power Exhaust 2 --- Pos 1 READ ONLY % pe2_pos1 AV:351 0TO1 PE2_POS1
Power Exhaust 2 --- Pos 2 READ ONLY % pe2_pos2 AV:352 0TO1 PE2_POS2
Power Exhaust 2 --- Pos 3 READ ONLY % pe2_pos3 AV:353 0TO1 PE2_POS3
P o w e r E x h a u s t 2 --- S p e e d 1 READ ONLY % pe2_spd1 AV:354 0TO1 PE2_SPD1
P o w e r E x h a u s t 2 --- S p e e d 2 READ ONLY % pe2_spd2 AV:355 0TO1 PE2_SPD2
P o w e r E x h a u s t 2 --- S p e e d 3 READ ONLY % pe2_spd3 AV:356 0TO1 PE2_SPD3
Power Exhaust 2 Starts READ ONLY st_pe_2 AV:149 0 TO 999999 ST_PE_2
Power Exhaust1 Run Hours READ ONLY hrs hour_pe_1 AV:61 0 TO 999999 HR_PE_1
Power Exhaust2 Run Hours READ ONLY hrs hour_pe_2 AV:62 0 TO 999999 HR_PE_2
Preocc Purge Duration R/W min iaqptime AV:252 5 TO 120 IAQPTIME
Preocc Purge Lockout OAT R/W °F iaqp_la AV:248 0TO70 IAQP_LA
Previous Unoccupied Time READ ONLY min prvuntim AV:182 --- 1 TO 10079 PRVUNTIM
RA Relative Humidity R/W % rarh AV:30 0TO1 RARH
RARH Assigned Channel R/W rarh_channel AV:33 0TO3 RARHCH AN
RARH Sensor Value @ 20mA R/W % rarh_20ma AV:32 0.0f TO 1 RARH20MA
RARH Sensor Value at 4mA R/W % rarh_4ma AV:31 0TO1.0f RARH_4MA
rdv_a Resets Count READ ONLY rs_rdv_a AV:389 0 TO 65535 RS_RDV_A
RDV_A Run Hours READ ONLY hrs hour_rdv_a AV:381 0 TO 999999 HR_RDV_A
rdv_a Starts READ ONLY st_rdv_a AV:385 0 TO 999999 ST_RDV_A
Reheat lev 1 Rst Count READ ONLY rs_rqhl1 AV:390 0 TO 65535 RS_RQHL1
Reheat lev 2 Rst Count READ ONLY rs_rqhl2 AV:391 0 TO 65535 RS_RQHL2
Reheat leve l 1 Run Hrs READ ONLY hrs hour_rqhl1 AV:382 0 TO 999999 HR_RQHL1
Reheat level 1 Starts READ ONLY st_rqhl1 AV:386 0 TO 999999 ST_RQHL1
Reheat leve l 2 Run Hrs READ ONLY hrs hour_rqhl2 AV:383 0 TO 999999 HR_RQHL2
Reheat level 2 Starts READ ONLY st_rqhl2 AV:387 0 TO 999999 ST_RQHL2
Req Compr DehumStgs R/W reqdstgs AV:413 0TO10 REQDSTGS
Requested Cooling Stages READ ONLY req_cstgs AV:292 0TO3 REQCSTGS
Requested Damper Pos R/W % dmpr_req_pos AV:4006 0TO1 DAMPRQ
Requested Heating Stages READ ONLY reqhstgs AV:293 0TO2 REQHSTGS
Request ed IDF Speed READ ONLY % req_fan_spd AV:35 0TO1 RQFANSPD
Reset Device R/W resetdev AV:184 0TO1 RESETDEV

Table of Contents