Settings -- Main Menu Layout (cont)
DISPLAY TEXT EXP ANDED DISPLAY TEXT VALUES UNITS DEFAUL T POINT ENTRY
AIR QUALITY Air Quality Configurations Menu
ANALOG IAQ CTRL Analog Input IAQ Co ntrol 0=NO IAQ,
1=DCV,
2=IAQ OVRD,
3=CTRL MINP
0: no FIOP
1: FIOP
IAQANCFG
IAQ POS @ MAX SPD IAQ Position at Max Fan 0 to 100 % 10 IAQMINP
LOW AIR.Q DIFF AQ Differential Low 0 to 5000 100 DAQ_LOW
HIGH AIR.Q DIFF AQ Differential High 0 to 5000 700 DAQ_HIGH
PREOCC PURGE ENBL IAQ Preoccupancy Purge Ye s/ No Yes IAQPURGE
PURGE POS @ MAX IAQ Purge Pos at Max IDF 0 to 100 % 40 IAQPMAX
PREOCC LOW LIMIT Preocc Purge Lockout OAT 0to70 °F 50 IAQP_LA
PREOCC PURGE TIME Preocc Purge Duration 5 to 120 min 15 IAQPTIME
A Q D I F H I --- IA Q O V R AQ Diff High IAQOVERRIDE 0 to 5000 PPM 700 AQD_HIGH
A Q D I F L O --- IA Q O V R AQ Diff Low--- IAQ OVERRIDE 0 to 5000 PPM 100 AQD_LOW
IAQ OVRRD ENABLE IAQ override enable Yes/ No No IAQOVREN
ALARM RELAY Alarm Relay Configurations Menu
ALM RELAY CHANNEL ALM Relay Assigned Chan 0=NONE,
1=MBB RLY11,
2=MBB RLY06
1=MBB RLY11 ALM_CHAN
THERMOSTAT ALERTS Thermostat Alerts Yes/No Yes TSTAT_AL
HARDWARE ALERTS Hardware Failures Alerts Yes/N o Yes HW_AL
SAT/RAT ALERTS SAT/RAT Sensor Alerts Yes/ No Yes SATRATAL
OAT SENSOR ALERTS OAT Thermistor Alerts Yes/No Yes OATRL_AL
SPACE SENS ALERTS Space Sensors Alerts Ye s/No Yes SPACE_AL
TRANSDUCER ALERTS Transducer Sensor Alerts Yes/ No Yes TRANS_AL
RH SENSOR ALERTS RH sensor failure Alert Ye s/ No Yes RHS_AL
CO2 SENSOR ALERTS Air Quality CO2 Alerts Yes/No Yes CO2S_AL
OACFM SENS ALERTS OACFM Alarm Relay Yes/ No No OACFM_AL
ECONOMIZER ALERTS Economizer Alerts Ye s/No Yes ECON_AL
AIRFILTERALERTS Dirty Filter Alerts Ye s/ No Yes FILT_AL
GEN STATUS ALERTS General Status Alerts Yes/No Yes GENS_AL
REFRIG CIR ALERTS Refrig Circuit Alerts Yes/No Yes CKT_AL
COMPRESSOR ALERTS Compressor Alerts Yes/ No Yes COMP_AL
HEATING ALERTS Heating Failure Alerts Yes/No Yes HEAT_AL
INDOOR FAN ALERTS Indoor Fan Alerts Ye s/ No Yes FAN_AL
ON ACTIVE FAUL TS Relay On Active Faults Ye s/ No Yes FAULT_AL
SERVICE CONFIG MENU Service Configuration Menu
CMP FRAMEWORK Compressor Framework 0=1CIR 2CMP,
1=1CMP+LDR,
2=1CMP
1: All except below
2: 48/50FC 04---06
SYSVTYPE
SHUTDWN A1 FIRST Comp A1 Shutdown First Yes/No No SDWN_A1
SHUTDWN ALD FIRST Comp Loader Shutdown 1st Ye s/ No Yes: All except below
No: 48/50FC 04--- 06
SDWN_ALD
IDF CURVE LO RPM IDF Curve Low End RPM 0 to 3000 RPM 189: Size 04 Standard
Static Fan
219: Size 04 Medium
Static Fan
249: Size 04 High
Static Fan
190: Size 05 Standard
Static Fan
217: Size 05 Medium
Static Fan
246: Size 05 High
Static Fan 230v
1ph
266: Size 05 High
Static Fan 230v
3ph, 460v, 575v
215: Size 06 Standard
Static Fan
239: Size 06 Medium
Static Fan
266: Size 06 High
Static Fan 230v
1ph
284: Size 06 High
Static Fan 230v
3ph, 460v, 575v
230: Size 07 Standard
Static Fan
253: Size 07 Medium
Static Fan
284: Size 07 High
Static Fan
IFMLORPM