147
APPENDIX E: BACnet Points List (cont)
Point Name Typ e
BACnet
Object ID
Alias
(CCN Point Name)
BACnet Object Name
Preocc Purge Lockout OAT BMAV AV:248 iaqp_la
Previous Unoccupied Time BMAV AV:182 prvuntim
RARH Channel Number BMAV AV:33 rarh_channel
RARH Sensor Value at 4mA BMAV AV:31 rarh_4ma
RARH Sensor Value at 20mA BMAV AV:32 rarh_20ma
Reheat Discharge V alve Resets Count BMAV AV:389 rs_rdv_a
Reheat Discharge Valve Run Hours BMAV AV:381 hour_rdv_a
Reheat Discharge Valve Starts BMAV AV:385 st_rdv_a
Reheating Liquid Valve Resets Count BMAV AV:456 rs_rlv_a
Reheating Liquid Valve Run Hours BMAV AV:458 hr_rlv_a
Reheat level 1 of Humidimizer Rst Count BMAV AV:390 rs_rqhl1
Reheat level 1 of Humidimizer Run Hrs BMAV AV:382 hour_rqhl1
Reheat level 1 of Humidimizer Starts BMAV AV:386 st_rqhl1
Reheat level 2 of Humidimizer Rst Count BMAV AV:391 rs_rqhl2
Reheat level 2 of Humidimizer Run Hrs BMAV AV:383 hour_rqhl2
Reheat level 2 of Humidimizer Starts BMAV AV:387 st_rqhl2
Reheat Liquid Valve Starts BMAV AV:460 st_rlv_a
Req Compr DehumStgs BMAV AV:413 reqdst gs
Requested Cooling Stages BMAV AV:292 req_cstgs
Requested Damper Pos BMAV AV:4006 damprq dmpr_req_pos
Requested Heating Stages BMAV AV:293 req_hstgs
Reset Device BMAV AV:184 resetdev
Restore Completion Time BMAV AV:337 rstcomtm
Return Air Enthalpy BMAV AV:95 ra_enth
Return Air Rel Humidity BMAV AV:30 rarh
Return Air Te mpe rature BMAV AV:1010 ra_t emp
SA Tempering Set point BMAV AV:411 sup_air_temp_setpt
Saturated Dischrg Pres A BMAV AV:124 sdp_a
Saturated Suction Pres A BMAV AV:131 ssp_a
Service Test Reset Count BMAV AV:116 rs_stest
Service Test Run Hours BMAV AV:63 hour_serv_tst
Service Test Starts BMAV AV:151 st_stest
Setpoint adjustment BMAV AV:6021 setadj setpt_adj
Single Zone Setpoint BMAV AV:6001 zonespt zone_setpoint
Software Build Time BMAV AV:169 fw_bldtm
Space Indoor Air Quality from Linkage BMAV AV:270 lnk_siaq
Space Relative H umidity BMAV AV:1011 space_rh
Space Relative Humidity from Linkage BMAV AV:271 lnk_sprh
Space RH OCC Setpoint BMAV AV:367 sprh_osp
Space RH UOCC Setpoint BMAV AV:461 sprh_usp
Space Temperature BMAV AV:2007 spt space_temp
Space Tempe rature Offset BMAV AV:1006 spto stpt_adj
SPRH Assigned Channel BMAV AV:372 sprhchan
SPRH Sensor Value at 4mA BMAV AV:375 sprh_4ma
SPRH Sensor Value at 20mA BMAV AV:373 sprh_20ma
SPT Offset Range (+/--- ) BMAV AV:298 spto_rng
SPT Offset Total diff BMAV AV:6020 sptodiff setpt_adj_limit
Standard Barometric Pressure BMAV AV:303 std_barp
Supply Air d/dt (F/min) BMAV AV:342 sattrend
Supply Air Temperature BMAV AV:1008 sat sa_temp
System Demand BMAV AV:37 sys_demand
System Demand Alert BMAV AV:227 sysdmat sys_dmd_alert
System Static Pressure BMAV AV:312 lnk_dsp lnk_ahu_static
System Touch AI for SPRH BMAV AV:8027 aistsprh
System Touch AI for SPT BMAV AV:8026 aistspt
System Touch Device BMAV AV:8024 devst
System Touch Poll Rate BMAV AV:8025 pollst
T24 Damper SAT deadband BMAV AV:308 t24satdb
T24Economizer Min Move for SAT BMAV AV:306 t24ecsts
T24 Heat/Cool End Delay BMAV AV:305 t24chdly
T24 Min Difference in RAT--- OAT BMAV AV:307 t24ratdf
T24 Test Maximum Position BMAV AV:310 t24tstmx
T24 Test MinimumPosition BMAV AV:309 t24tstmn
Test ODF All Output Spd BMAV AV:123 s_odfspd
Test ODF Output 1 Speed BMAV AV:120 s_odfsp1