APPENDIX E: BACnet Points List (cont)
Point Name Typ e
BACnet
Object ID
Alias
(CCN Point Name)
BACnet Object Name
Test ODF Output 2 Speed BMAV AV:121 s_odfsp2
Test ODF Output 3 Speed BMAV AV:122 s_odfsp3
TL O increment BMAV AV:6026 tloinc tlo_increment
TLO limit BMAV AV:6027 tlolim tlo_limit
TL O Time Remaining BMAV AV:6028 tlorem tlo_time_rem
UFC Low temp limit BMAV AV:287 oatlufc
UFC PreOcc Time BMAV AV:105 ufctime
Unit Full Load Run Hours BMAV AV :52 hr_fload hour_full_ld
Unit Full Load Starts BMAV AV:140 st_fload
Unit Startup delay BMAV AV:153 startdly
Unoccupied Cool Setpoint BMAV AV:8 ucsp unoccupied_cooling
Unoccupied Heat Setpoint BMAV AV:178 uhsp unoccupied_heating
Unoccupied Setpoint Gap BMAV AV:6004 udb unoccupied_deadband
Unoccupied Zone Setpoint BMAV AV:6005 usp unoccupied_setpoint
User Password BMAV AV:181 password
Value of Prime variable BMAV AV :39 prime
V ent Fan Reset Count BMAV AV:117 rs_ventf
V ent Fan Run Hours BMAV AV:64 hour_vent_fan
Ventilation Fan Starts BMAV AV:152 st_ventf
VFD1 Actual Motor Power (kw) BMAV AV:3006 vfd_out_kw
VFD1 Motor Amps BMAV AV:3002 outmcur vfd_motor_amps
VFD1 OUTPUT FREQ BMAV AV:3003 outmfreq vfd_out_frequency
VFD1 OUTPUT VOLTAGE BMAV AV:3004 outmvolt vfd_out_voltage
VFD1 Received Speed BMAV AV:3007 refspeed vfd_speed_req
VFD 1 Maximum Reference BMAV AV:68 maxref
VFD 1 Minimum Reference BMAV AV:72 minref
VFD 1 Ramp Down Time BMAV AV:29 rampdn_t ramp_down_time
VFD 1 Ramp Up Time BMAV AV:96 rampup_t ramp_up_time
VFD1 Motor Power (hp) BMAV AV:3005 outpwrhp vfd_out_hp
VFD Actual Speed BMAV AV:174 mav
VFD Alarm Code BMAV AV:158 a lmerrc
VFD Auto Restart Time BMAV AV:160 arstrt_t
VFD Current Limit BMAV AV :3 curr_limit
VFD DC Link V oltage BMAV AV:168 dclnvolt
VFD H eat Sink Temp BMAV AV:170 htsinkt
VFD KWH Output BMAV AV:171 kwhcntr
Zone Temperature BMAV AV:296 space_t zone_temp
ZS Zone Temp BMAV AV:1905 ZSZoneTemp
A012--- MBB Zero Crossing Alert BMBV BV:245 a_mbb0x
A015--- MBB RNET Voltage out of Range Alert BMBV BV:246 a_mbb12d
A016--- MBB 24VDC Voltage out of Range Alert BMBV BV:247 a_mbb24d
A017--- MBB 5VDC Voltage out of Range Alert BMBV BV:248 a_mbb5dc
A019--- MBB Time Clock Error Alert BMBV BV:237 a_notime
A100--- SAT Sensor Error Alert BMBV BV:188 a_badsat
A101--- FST out of Range Alert BMBV BV:185 a_badfst
A102--- FST Open Circuit Alert BMBV BV:193 a_opnfst
A103--- FST Short Circuit Alert BMBV BV:204 a_shtfst
A104--- OAT out of Range Alert BMBV BV:186 a_badoat
A105--- OAT Open Circuit Alert BMBV BV:196 a_opnoat
A106--- OAT Short Circuit Alert BMBV BV:207 a_shtoat
A107--- RAT out of Range Alert BMBV BV:187 a_badrat
A108--- RAT Open Circuit Alert BMBV BV:198 a_opnrat
A109--- RAT Short Circuit Alert BMBV BV:209 a_shtrat
A110--- SPT out of Range Alert BMBV BV:190 a_badspt
A111--- SPT Open Circuit Alert BMBV BV:201 a_opnspt
A112--- SPT Short Circuit Alert BMBV BV:212 a_shtspt
A130--- Circuit A SSP out of Range Alert BMBV BV:189 a_badspa
A131--- Circuit A SSP Open Circuit Alert BMBV BV:200 a_opnspa
A132--- Circuit A SSP Short Circuit Alert BMBV BV:211 a_shtspa
A133--- Circuit A SDP Out Of Range BMBV BV:183 a_baddpa
A134--- Circuit A SDP Open Circuit Alert BMBV BV:191 a_opndpa
A135--- Circuit A SDP Short Circuit Alert BMBV BV:202 a_shtdpa
A150 OACFM Open Circuit Alert BMBV BV:276 a_opnoac
A151 OACFM Short Circuit Alert BMBV BV:277 a_shtoac
A160--- OARH Open Circuit Alert BMBV BV:197 a_opnoarh