Settings -- Main Menu Layout (cont)
Display Text Expanded Text Range Units Default Point Entry
HEATING (cont) Heating Configurations Menu
HEAT FANOFF DELAY Heating Fan --- off Delay 10 to 600 sec 30 (50 series)
45 (48 seri es)
HEAT_FOD
HEAT LOCKOUT OAT Heating Lockout Temp 40 to 125 °F 75 OATLHEAT
SAT DURING HEAT? SAT Heat Mode Sensing Enable/Disable Disable SAT_HEAT
IGC IFO TIMEOUT No IGC IFO input Timeout 0to60 min 5 NO_IGCTM
PREHEAT W/O IDF? Pre --- Heat HX without IDF? Enable/Disable Disable PREHT_HX
PREHEAT FAN DELAY Pre---HeatFanOnDelay 0 to 120 sec 30 PREHT_TM
SA TEMPER ENABLED SupplyAirTemperingEnable Yes/No Yes SATEMPEN
SA TEMPER SET PNT SA tempering Set point xx °F 50 SATEMPSP
TEMPER MAX OUT Max OAT for SA tempering --- 40 to 125 °F 48 OATSTEMP
INDOOR FAN Indoor Fan Configurations Menu
OCCUPIED FAN? FanOnWhenOccupied Yes/ No Yes FANON_OC
INDOOR FAN TYPE Indoor Fan Type 0=None
1=VFD
2=Direct Drive
1 1=AllUnitsexceptsizes
04---06 fan option “0”
2=fanoption0onsizes
04---06
IDFTYPE
DIR DRV IDF SPDS Direct Drive Fan Speeds 2=2
3=3
2 2=fanoption0onsizes
04---06
NUMFSPDS
SHUTDOWN IDF FAIL Shut Down on IDF Failure Yes/No enum No FATALFAN
IDF VFD VOLTAGE IDF VFD Nom. Motor Volts 50 to 1000 volts See VFD Motor Default
Configuration Tables.
For sizes 04--- 06 see
Table 32.
For size 07--- 26 Vertical
units see Table 39.
F o r s i z e 0 7 --- 2 6 Ho ri z o n -
tal units see Table 40.
MOTVOLT
IDF VFD NOM. FREQ IDF VFD Nom. Motor Freq 20 to 400 Hz 60 MOTFREQ
IDF VFD NOM. AMPS IDF VFD Nom. Motor Amps 0.1 to 26.0 amps See VFD Motor Default
Configuration Tables.
For sizes 04--- 06 see
Table 32.
For size 07--- 26 Vertical
units see Table 39.
F o r s i z e 0 7 --- 2 6 Ho ri z o n -
tal units see Table 40.
MOTCUR
IDF VFD NOM. RPM IDF VFD Nom. Motor RPM 100 to 60000 rpm See VFD Motor Default
Configuration Tables.
For sizes 04--- 06 see
Table 32.
For size 07--- 26 Vertical
units see Table 39.
F o r s i z e 0 7 --- 2 6 Ho ri z o n -
tal units see Table 40.
MOTNOMSP
IDF VFD MIN REF IDF VFD Min Reference 0 to 65.0 Hz 0 MINREF
IDF VFD MAX REF IDF VFD Max Reference 0 to 65.0 Hz 60 MAXREF
VFD ACCEL. TIME IDF VFD Accel. Time 1 to 1800 sec 10 RAMPUP_T
VFD DECEL. TIME IDF VFD Decel. Time 1 to 1800 sec 10 RAMPDN_T
IDF VFD AMP LIMIT IDF VFD Current Limit 0 to 300 100 CURRLMT
IDF VFD TIMEOUT IDF VFD Comm time out 1 to 600 sec 30 CNT_TOUT
IDF VFD RESET DUR IDF VFD Auto Reset time 0 to 600 sec 30 ARSTRT_T
VFD RFI FILTER IDF VFD RFI Filter On/Off On RFIFIL TR
ECONOMIZER Economizer Configurations Menu
ECON INSTALLED? Economizer Installed? Ye s/No No: no FIOP
Yes: F IOP
ECONO
ECON MAX POS Econ Max Damper Position 0 to 100 % 100 DAMPMAX
ECON TRAVEL TIME Economizer Travel Time 5 to 300 sec 150 ECONOTRV
MINIMUM POSITION CONFIGS Minimum Position Configurations menu
MIN POS @ MAX FAN Econ Min at Max Fanspeed 0 to 100 % 30 MINP_MAX
MIN POS SPEED 1 Min Pos --- User Speed 1 0 to 100 % 0 MP_USPD1
MIN POS DAMP 1 M i n P o s --- U s e r P o s 1 0 to 100 % 0 MP_UPOS1
MIN POS SPEED 2 Min Pos --- User Speed 2 0 to 100 % 0 MP_USPD2
MIN POS DAMP 2 M i n P o s --- U s e r P o s 2 0 to 100 % 0 MP_UPOS2
MIN POS SPEED 3 Min Pos --- User Speed 3 0 to 100 % 0 MP_USPD3
MIN POS DAMP 3 M i n P o s --- U s e r P o s 3 0 to 100 % 0 MP_UPOS3
FREE COOL CONFIGS Free Cooling Spec ific Config u r at ions
Menu
LOW COOL SAT SP Low Free Cool SAT Setpnt 40 to 80 °F 65 LCSASP
HIGH COOL SAT SP High FreeCool SAT Setpnt 40 to 80 °F 55 HCSASP
FREE COOL MAX OAT Free Cooling Max OAT 0to90 °F 65 MAXFREET
FREE COOL MIN OAT Free Cooling Min Temp --- 30 to 70 °F 0 MINFREET
DIFF DRY BULB CTL Diff. Dry Bulb Control Enable/Disable Disable DIFFBULB
DIFF DB DEADBAND Diff. Dry Bulb Deadband 0to20 °F 3 OA TRATDB
ENTHALPY HI LIMIT Max Enthalpy OA limit 1.0 to 99.0 Btu/lb 28 FREEM AXE
DIFF ENTHALPY CTL Diff. Enthalpy Control Enable/Disable Disable DIFFENTH
ENTHALPY DEADBAND Enthalpy Cross Deadband 0 to 20.0 Btu/lb 2 OAERAEDB
E C O N O P I D --- K P Economizer PID --- kP 0.00 to 99.90 2.5 ECONO_P
E C O N O P I D --- K I Economizer PID --- kI 0.00 to 99.90 0.12 ECONO_I
E C O N O P I D --- K D Economizer PID --- kD 0.00 to 99.90 1 ECONO_D
E C O N O P I D --- R A T E Economizer PID --- rate 10 to 180 sec 15 ECONO_DT