Settings -- Main Menu Layout (cont)
Display Text Expanded Text Range Units Default Point Entry
ECONOMIZER (cont) Economizer Configurations Menu
UNOCCUPIED FREE COOL Unoccupied Free Cooling Configs Menu
WHEN TO UNOCC FC When to Unocc Free Cool? 0=Disabled,
1=PreOcc,
2=Unocc
1=PreOcc UFC_CFG
UFCPREOCCTIME UFC PreOcc Time 1 to 999 min 120 UFCTIME
UFC LOW TEMP Unocc Free Cool Low Temp ---30 to 70 °F 50 OATLUFC
POWER EXHAUST CONFIGS Power Exhaust Configurations Menu
PE1 RELAY CHANNEL PE1 Relay Channel 0=NONE,
1=MBB RLY11,
2=MBB RLY06
0: no FIOP
2: FIOP
PE1_CHAN
PE1 POS @ MAX SPD PE Stage 1 at Max speed 0 to 100 % 40 PE1_PMAX
PE OFF DEADBAND PE Turn Off Dead band 0 to 100 % 5 PE_OFFDB
PE2 RELAY CHANNEL PE2 Relay Channel 0=NONE,
1=MBB RLY11,
2=MBB RLY06
0=None PE2_CHAN
PE2 POS @ MAX SPD PE Stage 2 at max speed 0 to 100 % 75 PE2_PMAX
ECON DISCONNECT
DIAG N O ST I C
Econ Actuator Mechanical disconnect
diagnostic menu
M D D --- H / C E N D D LY T24 Heat/Cool End Delay 0to60 min 25 T24CHDLY
MDD--- MIN MOVE T24Econ Min Move for SAT 10 to 20 % 10 T24ECSTS
M D D --- S A T D B Damper SAT deadband 0 to 20.0 °F 12 T24SATDB
M D D --- M I N R AT --- O A T T24 Min Diff in RAT--- OAT 5.0 to 20.0 °F 15 T24RATDF
MDD--- MIN TEST POS T24 Test Minimum Pos 0 to 100 % 15 T24TSTMN
MDD--- MAX TEST POS T24 Test Maximum Pos 0 to 100 % 85 T24TSTMX
AIR QUALITY Air Quality Configurations Menu
ANALOG IAQ CTRL Analog Input IAQ Control 0=NO IAQ,
1=DCV,
2=IAQ OVRD,
3=CTRL MINP
0: no FIOP
1: FIOP
IAQANCFG
IAQ POS @ MAX SPD IAQ Position at Max Fan 0 to 100 % 10 IAQMINP
LOW AIR.Q DIFF AQ Differential Low 0 to 5000 ppm 100 DAQ_LOW
HIGH AIR.Q DIFF AQ Differential High 0 to 5000 ppm 700 DAQ_HIGH
PREOCC PURGE ENBL IAQ Preoccupancy Purge Yes/No Yes IAQPURGE
PURGE POS @ MAX IAQ Purge Pos at Max IDF 0 to 100 % 40 IAQPMAX
PREOCC L OW LIMIT Preocc Purge Lockout OAT 0to70 °F 50 IAQP_LA
PREOCC PURGE TIME Preocc Purge Duration 5 to 120 min 15 IAQPTIME
A Q D I F H I --- IA Q O V R AQ Diff High IAQOVERRIDE 0 to 5000 PPM 700 AQD_HIGH
A Q D I F LO --- IA Q O V R AQ Diff Low--- IAQ OVERRIDE 0 to 5000 PPM 100 AQD_LOW
IAQ OVRRD ENABLE IAQ override enable Ye s/No enum No IAQOVREN
ALARM RELAY Alarm Relay Configurations Menu
ALM RELAY CHANNEL ALM Relay Assigned Chan 0=NONE,
1=MBB RLY11,
2=MBB RLY06
1=MBB RLY11 ALM_CHAN
THERMOSTAT ALERTS Thermostat Alerts Ye s/No Yes TSTAT_AL
HARDWARE ALERTS Hardware failures Alerts Yes/No Yes HW_AL
SAT/RAT ALERTS SAT/RAT Sensor Alerts Ye s/No Yes SATRATAL
OAT SENSOR ALERTS OAT Thermistor Alerts Yes/ No Yes OATRL_AL
SPACE SENS ALERTS Space Sensors Alerts Yes/ No Yes SPACE_AL
TRANSDUCER ALERTS Transducer Sensor Alerts Yes/ No Yes TRANS_AL
RH SENSOR ALERTS RH sensor failure Alert Yes/No Yes RHS_AL
CO2 SENSOR ALERTS Air Quality CO2 Alerts Yes/No Yes CO2S_AL
OACFM SENS ALERTS OACFM Alarm Relay Yes/No Ye s OACFM_AL
ECONOMIZER ALERTS Economizer Alerts Yes/ N o Yes ECON_AL
AIRFILTERALERTS Dirty Filter Alerts Yes/ No Yes FILT_AL
GEN STATUS ALERTS General Status Alerts Yes/No Yes GENS_AL
REFRIG CIR ALERTS Refrig Circuit Alerts Yes/ No Yes CKT_AL
COMPRESSOR ALERTS Compressor Alerts Yes/No Yes COMP_AL
HEATING ALERTS Heating failure Alerts Ye s/No Yes HEAT_AL
INDOOR FAN ALERTS Indoor Fan Alerts Yes/ No Yes FAN_AL
VFD ALERTS VFD Alerts Ye s/No Yes VFD_AL
IO BOARD ALERTS Relay On Active IOBA Yes/No
No
IOBFA_AL
ON ACTIVE FAULTS Relay o n Active Faults Ye s/No Yes FAULT_AL
NEW HARDWARE Quick Menu for New Hardware
UNIT CONTROL TYPE Unit Co ntrol Type 0=TSTAT,
1=SPACE SEN,
2=RAT SEN
0=TSTAT CTRLTYPE
ECON INSTALLED? Economizer Installed? Ye s/No No: no FIOP
Yes: F IOP
ECONO
SPRH SENS CHANNEL SPRH Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08,
4=SIOB Ai10
0=None SPRHCHAN
IAQ SENSOR CHAN IAQ Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
1: no FIOP
0: FIOP
IAQ_CHAN
OAQ SENSOR CHAN OAQ Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0=None OAQ_CHAN