160
Settings -- Main Menu Layout (cont)
Display Text Expanded Text Range Units Default Point Entry
NEW HARDWARE (cont) Quick Menu for New Hardware
OARH SENSOR CHAN OARH Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
3: no FIOP
0: FIOP
OARHCHAN
RARH SENS CHANNEL RARH Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0=None RARHCHAN
OACFM SENS CHANNEL OACFM Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08,
4=SIOB Ai10
0=None OCFM CHAN
FIRE SHUTDOWN SW Fire Shutdown Switch 0=NORM OPEN,
1=NORM CLSD,
2=NO SWITCH
2: no FIOP
0: FIOP
FIRE_CFG
FILTER SW CHANNEL Filter Status Sw Channel 0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None FILTCHAN
REMOTE OCC CHAN Remote Occupancy Channel 0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None RMOCCHAN
REM.SHUTDOWN CHAN Remote Shutdown Channel 0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None ROFFCHAN
COFS CHANNEL COFS Assigned Channel 0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None COFSCHAN
GEN STATUS CHAN General Status Channel 0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None GEN_CHAN
ENTHALPY SW CHAN Enthalpy Sw Channel 0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None ENTHCHAN
SIOB1 INSTALLED SIOB 1 Enabled Yes/No No for all except
Humidimizer units
SIOB1_EN
NETWORK SETTINGS Building Network Configurations Menu
BAS PROTOCOL BAS Protocol Select 0=NONE,
1=CCN,
2=BACNET
x 0=NONE BMS_CFG
NETWORK TIMEOUT Network Input Timeout 0 to 600 min 30 NETINTO
CCN CCN Network Configuration Menu
BUS NUMBER CCN Bus Number 0 to 239 0 CCNBUS
CCN ELEMENT # CCN Element Number 1 to 239 1 CCNADD
CCN BAUDRATE CCN Baud Ra te 0=9600,
1=19200,
2=38400
2=38400 BAUDENUM
BROADCAST ACK? CCN Broadcast Ackāer Yes/ No No CCNBCACK
BROADCAST SCHEDL? Global Schedule Broadcst Yes/ No No CCN_GSBC
BROADCAST TIME? CCN Time Broadcast Yes/ No No CCNBC
BROADCAST OAT? Broadcast OAT On Network Yes/ No No OATBC
BROADCAST OARH? Broadcast OARH On Netwrk Yes/No No OARHBC
BROADCAST OAQ? Broadcast OAQ On Network Yes/No No OAQBC
BROADCAST IAQ? Broadcast IAQ On Network Ye s/No No IAQBC
LOCATION Device Location text string <bla nk> DEV_LOC
REFERENCE NUMBER Reference number text string <blank> REF_NUM
BACNET BACnet network configuration menu
MAC ADDRESS BACnet Device Macaddress 1 to 127 01 BAC_MAC
BACNET BAUDRATE BACnet BMS baud rate 0=9600,
1=19200,
2=38400,
3=57600,
4=76800,
5=115200
4=76800 BAC_BAUD
AUTO ID SCHEME ALC Auto Id Scheme Yes/ No Yes AUID
BACNET AUTO ID BACnet ID Auto ID Yes/No Yes BAC_AUID
BACNET ID BACnet ID Number 0 to 4194302 1610101 BAC_ID
LINKAGE SETTINGS LINKAGE SETTINGS MENU
DEVICE IAQ BACnet device for IAQ 0 to 4194303 1610100 DEVIAQ
OBJECT ID IAQ Object instance for IAQ 0 to 9999 1009 OBJIAQ
COV IAQ Change of value for IAQ 0to60 0 COVIAQ
DEVICE OAQ BACnet device for OAQ 0 to 4194303 1610100 DEVOAQ