APPENDIX A: SystemVut Controller Display
Settings Main Menu Layout (cont)
Display Text Expanded Text Range Units Default Point
CLOCK (cont) Clock Adjust ment Menu
DST START MONTH DST Start Month 1=JANUARY,
2=FEBRUARY,
3=MARCH,
4=APRIL,
5=MAY,
6=JUNE,
7=JULY,
8=AUGUST,
9=SEPTEMBER,
10=OCTOBER,
11=NOVEBER,
12=DECEMBER
3 ST ARTM
DST ST ART WEEK DST Start Week 1to5 2 ST ARTW
DST START DAY DST Start Day 1=MONDAY,
2=TUESDAY,
3=WEDNESDAY,
4=THURSDAY,
5=FRIDAY,
6=SATURDAY,
7=SUNDAY
7 ST ARTD
DST MINS TO ADD DST Minutes to Add 0to90 min 60 MINADD
DST STOP MONTH DST Stop Month 1=JANUARY,
2=FEBRUARY,
3=MARCH,
4=APRIL,
5=MAY,
6=JUNE,
7=JULY,
8=AUGUST,
9=SEPTEMBER,
10=OCTOBER,
11=NOVEBER,
12=DECEMBER
1 STOPM
DST STOP WEEK DST Stop Week 1to5 1 STOPW
DST ST OP DAY DST Stop Day 1=MONDAY,
2=TUESDAY,
3=WEDNESDAY,
4=THURSDAY,
5=FRIDAY,
6=SATURDAY,
7=SUNDAY
7 STOPD
DST MINS TO SUB DST Minutes to Subtract 0to90 min 60 MINSUB
START TIME IN DA Y Time in day to start DST 0 to 600 min 120 DST_TOD
SCHEDULES Schedules Adjustment Menu
SCHEDULE NUMBER CCN Schedule Number 0 = Always Occupied,
1 --- 6 4 = L o c a l S c h e d u l e ,
65--- 99 = Global Schedule
0 SCHEDNUM
OCCUPANCY SCHEDULE OCCUPANCY SCHEDULE DATA
HOLIDAYS Holiday adjustment Menu
ALLOW G. HOLIDAY? Accept Global Holidays? Yes/No No HOLIDAYT
TIMED OVR LENGTH Timed Override Duration 0to4 hours 4 OTL_CFG
UNIT CONFIGURATIONS Unit Configurations Menu
GENERAL General Unit Configurations Menu
STARTUP DELAY Unit Startup Delay 10 to 600 sec 30 STARTDLY
UNIT CONTROL TYPE Unit Control Type 0=TSTAT,
1=SPACE SEN,
2=RAT SEN
0=TSTAT CTRLTYPE
THERMOSTAT TYPE Thermostat Hardware Type 0=CONV 2C2H,
1=DIGI 2C2H,
2=CONV 3C2H,
3=DIGI 3C2H
4=DIGI 2C2H_S
2=CONV 3C2H ST ATTYPE
ADAPTIVE TSTAT Tstat Adaptive Staging Yes/No Yes ADPTSTAT
DIRTY FILTER TIME Change Filter Timer 0 to 9999 hours 600 FILTLIFE
TEST MODE TIMEOUT Test inactivity time out 0=Disabled,
1=30 minutes,
2=1 hour,
3=2 hours,
4=4 hours,
5=8 hours,
6=12 hours
4=4 hours TEST_ITO
CCH MAX TEMP CCH Max Temperature 40 to 90 °F 65 CCHMAXT
STD BARO PRESSURE Std Baromet ric Pressure 13.00 to 35.00 in.Hg 29.92 STD_BARP
LINK STAGEUP TIME Linkage Stage inc. time 60 to 600 sec 180 LSTAGINC
UNIT’S MAX SAT Unit’s Maximum SAT 130 to 210 °F 200 UMAX_SAT
AUTO SAT FAULTS? Auto Clr SAT Limit Fault Yes/No No SATLACLR
ADAPTIVE TCS? Adaptive Temp Comp Start Enable/Disable Yes TCS_CFG
USER TCS BIASTIME User TCS Start bias time 0 to 180 min 0 TCSUBIAS