29
Red LED-Status
C08452
Fig. 40 -- Integrated Gas Control (IGC) Board
Table 9 IGC Connections
TERMINAL LABEL POINT DESCRIPTION SENSOR LOCATION TYPE OF I/O
CONNECTION
PIN NUMBER
INPUTS
RT, C Input power from TRAN 1 control box 24 VAC
SS Speed sensor gas section analog input J1, 1 -3
FS, T1 Flame sensor gas section switch input
W Heat stage 1 CTB 24 VAC J2, 2
RS Rollout switch gas section switch input J2, 5-6
LS Limit switch fan section switch input J2, 7-8
CS Centrifugal switch (not used) switch input J2, 9 -10
OUTPUTS
L1, CM Induced draft combustion motor gas section line VAC
IFO Indoor fan control box relay J2, 1
GV Gas valve (heat stage 1) gas section relay J2, 11-12