Table 10 – Orifice Sizes
ORIFICE
DRILL SIZE
CARRIER
PART NUMBER
DRILL
DIA. (in.)
#30 LH32RF129 0.1285
1/8 LH32RF125 0.1250
#31 LH32RF120 0.1200
#32 LH32RF116 0.1160
#33 LH32RF113 0.1130
#34 LH32RF111 0.1110
#35 LH32RF110 0.1100
#36 LH32RF105 0.1065
#37 LH32RF104 0.1040
#38 LH32RF102 0.1015
#39 LH32RF103 0.0995
#40 LH32RF098 0.0980
#41 LH32RF096 0.0960
#42 LH32RF094 0.0935
#43 LH32RF089 0.0890
#44 LH32RF086 0.0860
#45 LH32RF082 0.0820
#46 LH32RF080 0.0810
#47 LH32RF079 0.0785
#48 LH32RF076 0.0760
#49 LH32RF073 0.0730
#50 LH32RF070 0.0700
#51 LH32RF067 0.0670
#52 LH32RF065 0.0635
#53 LH32RF060 0.0595
#54 LH32RF055 0.0550
#55 LH32RF052 0.0520
#56 LH32RF047 0.0465
#57 LH32RF043 0.0430
#58 LH32RF042 0.0420
Table 11 – Altitude Compensation
}
(48LCD/E/F/S/R/T*04--06)
ELEVATION
ft (m)
72,000 BTUH
Nominal
115,000 BTUH
Nominal
150,000 BTUH
Nominal
NG
Orifice Size
LP
Orifice Size
NG
Orifice Size
LP
Orifice Size
NG
Orifice Size
LP
Orifice Size
0 --- 2000 (610) 33
1
51
4
33
1
50
3
†30 46
3
2000 (610) 35
1
51
4
35
1
51
4
†30 47
3
3000 (914) 35
1
52
4
35
1
51
4
31
1
47
3
4000 (1219) 36
1
52
4
36
1
51
4
31
1
48
3
5000 (1524) 36
1
52
4
36
1
51
4
31
1
48
3
6000 (1829) 37
2
52
4
37
2
52
4
31
1
48
3
7000 (2134) 38
2
53
4
38
2
52
4
32
1
49
3
8000 (2438) 39
2
53
4
39
2
52
4
33
1
49
3
9000 (2743) †40 53
4
†40 53
4
34
1
50
3
10000 (3048) †41 54
4
†41 53
4
35
1
50
3
11000 (3353) †42 54
4
†42 53
4
36
1
51
4
12000 (3658) †43 54
4
†43 54
4
37
2
51
4
13000 (3962) †43 55
4
†43 54
4
38
2
52
4
14000 (4267) 44
2
†56 44
2
55
4
†40 53
4
LEGEND
NG = Natural Gas LP = Liquid Propane
} As the height above sea level increases, there is less oxy-
gen per cubic ft. of air. Therefore, heat input rate should
be reduced at higher altitudes.
{ Not included in kit. May be purchased separately through
dealer.
1 = CRLPELEV001A00
2 = CRLPELEV002A00
3 = CRLPELEV003A00
4 = CRLPELEV004A00