105
Table D — Service Main Menu Layout
DISPLAY EXPANDED TEXT VALUES UNITS WRITE STATUS POINT
SERVICE Service Menu
UNIT TESTS Unit Tests Menu
TEST MODE Service Test Mode Enable On/Off Command
SERVICE TEST Service Test Menu
INDEPENDENTS INDEPENDENT TEST MENU
ECON POS TEST Economizer Position Test 0 to 100 % Command S_DAMPER
BUMP COMP A1 TEST Compressor Bump A1 Test On/Off Command S_BMPA1
BUMP COMP A2 TEST Compressor Bump A2 Test On/Off Command S_BMPA2
LIQ DV VALVE TEST Liq Diverter Val Rly Tst On/Off Command S_LDV_A
RH DIS VALVE TEST Rht Dischg Valve Rly Tst On/Off Command S_RDV_A
RH LIQ VALVE TEST Reheat Liq Valv Rly Test On/Off Command S_RLV_A
CL LIQ VALVE TEST Cooling Liq Valv Test On/Off Command S_CLV_A
CCH RELAY 1 TEST Crankcase Heater 1 test On/Off Command S_CCHR1
ALARM RELAY TEST Alarm Output Relay Test On/Off Command S_ALARM
PE1 RELAY TEST Power Exhaust 1 Test On/Off Command S_PE_1
PE2 RELAY TEST Power Exhaust 2 Test On/Off Command S_PE_2
FAN TESTS
Indoor and Outdoor Fan Tests
Menu
IDF SPEED TEST Indoor Fan Speed Test 0 to 100 % Command S_IDFSPD
ALL ODF SPD TEST System ODF speed test 0 to 1200 rpm Command S_ODFSPD
ODF 1 SPEED TEST Outdoor Fan 1 speed test 0 to 1200 rpm Command S_ODFSP1
ODF 2 SPEED TEST Outdoor Fan 2 speed test 0 to 1200 rpm Command S_ODFSP2
ODF 3 SPEED TEST Outdoor Fan 3 speed test 0 to 1200 rpm Command S_ODFSP3
IDF MANUAL TRANS IDF Manual Transition Yes/No Command S_IDFTRN
ODF MANUAL TRANS ODF Manual Transition Yes/No Command S_ODFTRN
COOL TESTS Cooling Test Menu
COOL A1 TEST Cooling W/Comp. A1 Test On/Off Command S_COOLA1
COOL A2 TEST Cooling W/Comp. A2 Test On/Off Command S_COOLA2
COOL ALD TEST Cooling W/Comp.ALD Test On/Off Command S_COLALD
IDF SPEED TEST Indoor Fan Speed Test 0 to 100 % Command S_IDFSPD
ALL ODF SPD TEST System ODF speed test 0 to 1200 rpm Command S_ODFSPD
HUMIDIMIZER TEST Humidi-MiZer Level Test
0=Off,
1=Subcool,
2=Reheat
Command S_HMZLEV
HEAT TESTS Heating Test Menu
HEAT 1 TEST Heating Stage 1 Test On/Off Command S_HEAT1
HEAT 2 TEST Heating Stage 2 Test On/Off Command S_HEAT2
IDF SPEED TEST Indoor Fan Speed Test 0 to 100 % Command S_IDFSPD
AUTOMATIC TEST Automatic Test Menu
AUTO INDP TEST AUTO INDEPENDENT TEST Yes/No Command AUTOINDP
AUTO COOL TEST RUN AUTO COOLING TEST Yes/No Command AUTOCOOL
AUTO HEAT TEST RUN AUTO HEATING TEST Yes/No Command AUTOHEAT
AUTO SYSTEM TEST RUN AUTO SYSTEM TEST Yes/No Command AUTOSYS
UNIT INFORMATION Unit Information Menu
MODEL # Equipment Model number xxxxxxxxxxxxxxxxxx Command EQ_MOD
SERIAL # Equipment Serial number xxxxxxxxxx Command EQ_SER
ENTER MODEL NUMBER Edit Equipment Model Number
VERSIONS Versions Menu
LC MAIN APP Application SW Version CESR131651-xx-xx FW_CESR
IDF VFD VFD1 SW Version text VFD1_SW
IO BOARD SIOB1 SW Version CESR131581-xx-xx SIOB1_SW
BOOTLOADER Bootloader SW Version CESR131659-xx-xx BL_CESR
USER MEASURED DATA User Measured Data Menu
SUPPLY VOLTAGE L1 Supply Voltage Leg 1 0 to 700.0 volt Command L1VOLTS
SUPPLY VOLTAGE L2 Supply Voltage Leg 2 0 to 700.0 volt Command L2VOLTS
SUPPLY VOLTAGE L3 Supply Voltage Leg 3 0 to 700.0 volt Command L3VOLTS
COMP A1 AMPS L1 Comp A1 Amps Leg 1 0 to 100.0 amps Command CA1L1_A
COMP A1 AMPS L2 Comp A1 Amps Leg 2 0 to 100.0 amps Command CA1L2_A
COMP A1 AMPS L3 Comp A1 Amps Leg 3 0 to 100.0 amps Command CA1L3_A
COMP A2 AMPS L1 Comp A2 Amps Leg 1 0 to 100.0 amps Command CA2L1_A
COMP A2 AMPS L2 Comp A2 Amps Leg 2 0 to 100.0 amps Command CA2L2_A
COMP A2 AMPS L3 Comp A2 Amps Leg 3 0 to 100.0 amps Command CA2L3_A
APPENDIX A — SYSTEMVU™ CONTROLLER DISPLAY