Fig. 12 — Outdoor Fan Motor Arrangement
Optional Humidi-MiZer Dehumidification System
Units with the factory-installed Humidi-MiZer system option
are capable of providing multiple modes of improved dehu-
midification as a variation of the normal cooling cycle. The
Humidi-MiZer system option includes additional valves in the
liquid line and discharge line of each refrigerant circuit, a re-
heat coil downstream of the evaporator, and variable-speed
control of all the outdoor fans. The Humidi-MiZer system
equipped configuration is factory set to Yes for Humidi-MiZer
system equipped units (HUMIDIMIZER OK = YES). This en-
ables Humidi-MiZer system operating modes and service test.
Humidi-MiZer system operation requires the installation and
configuration of a relative humidity switch input or a space rel-
ative humidity sensor. The HUMIDISTAT and SPRH leads are
provided with quick connects. The Space Humidity Switch
configuration, SETTINGS UNIT CONFIGURATIONS
SWITCH INPUTS CONFIGS HUMSTAT CHANNEL
identifies the normally open or normally closed status of this
input at high humidity. The Space RH Sensor configuration,
SETTINGS UNIT CONFIGURATIONS ANALOG IN-
PUTS CONFIGS SPRH SENS CHANNEL, identifies to
the channel number the sensor is wired into.
DEHUMIDIFICATION DEMAND
When using a humidistat or switch input, the demand for dehu-
midification is seen as Space Humidity Switch (INPUTS
SWITCH INPUTS HUMIDISTAT) being Low or High. A
low value means humidity level is good and a high value
means that dehumidification is needed.
When using an SPRH sensor, the demand is based on the Space
Humidity Sensor (INPUTS ANALOG INPUTS SPRH)
value compared to the Space RH Setpoint (SETTINGS
SPACE SETPOINTS  SPRH SETPOINT). If the Space
Humidity Sensor (SPRH) value is above the Space RH Set-
point (SPRH Setpoint), then dehumidification is needed. If the
Space Humidity Sensor (SPRH) value is below the Space RH
Setpoint (SPRH Setpoint) minus the Space RH Deadband
(SETTINGS  UNIT CONFIGURATIONS COOLING
 SPRH DEADBAND), then dehumidification is no longer
needed.
NOTE: When there is a dehumidification demand, the economizer
damper position is limited to its minimum damper position.
HUMIDI-MIZER SYSTEM MODES
With Humidi-MiZer system units, there are two additional HVAC
modes available for the user: Dehumidification and Dehum/Mech
Cooling. Selection of the Dehum/Mech Cooling mode is deter-
mined by the dehumidification demand and the cooling demand.
Tables 13 and 14 show the corresponding circuit mode and output
status for the different demand combinations.
48/50LC 24-26 48/50LC 17-20 48/50 LC14
OFM1
OFM5
OFM6
OFM4
OFM3
OFM2
Control Box Side
1
1
2
2
33
OFM1
OFM4
OFM3
OFM2
Control Box Side Control Box Side
2
1
2
1
OFM1
OFM3
OFM2
48/50LC 08-12
48/50LC 07
OFM1
OFM3
OFM2
Control Box Side
OFM1
OFM2
Control Box Side
Indicates the Outdoor
Fan Signal from the
board. Otherwise the
motor and signal match.
1
2
3
OFM
48/50LC 04-06
Control Box Side

Table of Contents

Other manuals for Carrier 48LC Series

Related product manuals