Table H — MODE — RUN STATUS
ITEM EXPANSION RANGE UNIT WRITE STATUS POINT
RUN STATUS
VIEW Auto View of Run Status
MODE Operating Mode see Appendix B MODETEXT
SUBM Operating Sub-Mode see Appendix B SUBMTEXT
S.DMD System Demand see Appendix B SYS_DMDT
LINK Linkage Active Yes/No YES LNK_ACT
OCC Currently Occupied Yes/No YES OCCUPIED
SAT Supply Air Temperature xxx.x °F SAT
COOL Cooling Status Menu
LA.ST Low Ambient Ctrl Status
0=Normal,
1=Entering,
2=Low Ambient,
3=Exiting
LACTRLST
RDHL Requested Dehum Level 0 to 2 REQDHLEV
MC.ON Mechanical Cool active? Yes/No MECHCOOL
MAX.C Max Allowed Cool Stages 0 to 3 YES MAXCSTGS
REQ.C Requested Cooling Stages 0 to 3 REQCSTGS
ACT.C Actual Cool Stage Active x ACTCSTGS
TG.A1 Compressor A1 Timeguard xxx sec TIMGD_A1
TG.A2 Compressor A2 Timeguard xxx sec TIMGD_A2
TG.AL Cmp Loader Timeguard xxx sec TIMG_ALD
FC.ON Free Cooling Active Yes/No FREECOOL
RDHS Req Compr Dehum Stgs 0 to 3 REQDSTGS
HEAT Heating Status Menu
REQ.H Requested Heating Stages 0 to 2 REQHSTGS
ACT.H Actual Heat Stage Active x ACTHSTGS
MAX.H Max Allowed Heat Stages 0 to 2 YES MAXHSTGS
TG.H1 Heat Stage 1 Timeguard xxx sec TIMGD_H1
TG.H2 Heat Stage 2 Timeguard xxx sec TIMGD_H2
VENT Ventilation Status Menu
VENT Ventilation Status see Appendix B VENTTEXT
EC.MP Min Position in Effect xxx % YES MIN_POS
OCC Currently Occupied Yes/No YES OCCUPIED
I.FAN Indoor Fan Status Menu
M.CUR IDF VFD Output Amps 0 to 655.35 OUTMCUR
M.HP IDF VFD Output Power hp 0 to 1000 OUTPWRHP
VFD.F IDF VFD Fault Detail
0=NONE,
1=PWR CARD,
2=EARTH FLT,
3=CTRL WORD,
4=OVER CURR,
5=OVER TEMP,
6=OVERLOAD,
7=UNDERVOLT,
8=OVER VOLT,
9=SHORT CIR,
10=PHASELOSS,
11=U LOSS,
12=V LOSS,
13=W LOSS,
14=CTRL VOLT,
15=VDD LOW,
16=MULTIPLE,
17=UNEXPECT
SVFDFLT
VFD.W IDF VFD Warning Detail
0=NONE,
1=VOLTAGE,
2=CURRENT,
3=THERMAL,
4=MULTIPLE,
5=UNEXPECT
SVFDWAR
A.IO Assigned I/O Channels
AI06 Assigned AI06 Function
0=None,
1=IAQ,
2=OARH,
3=RARH,
4=OAQ,
5=SPRH,
6=OACFM
MBBAI06F
APPENDIX C — NAVIGATOR™ DISPLAY