126
I.FAN (cont)
N.VLT IDF VFD Motor Volts 50 to 1000
See VFD Motor Default
Configuration Tables.
Table 35 (sizes 04-06)
Table 42 (Vert. sizes
07-26)
Table 43 (Horz. Sizes
14-26)
MOTVOLT
N.FRQ IDF VFD Motor Freq. 20 to 400 60 MOTFREQ
N.AMP IDF VFD Motor Current 0.1 to 40
See VFD Motor Default
Configuration Tables.
Table 35 (sizes 04-06)
Table 42 (Vert. sizes
07-26)
Table 43 (Horz. Sizes
14-26)
MOTCUR
N.RPM IDF VFD Motor Nom. RPM 100 to 60000
See VFD Motor Default
Configuration Tables.
Table 35 (sizes 04-06)
Table 42 (Vert. sizes
07-26)
Table 43 (Horz. Sizes
14-26)
MOTNOMSP
MN.RF IDF Danfoss Min Ref 0 to 65 0 MINREF
MX.RF IDF Danfoss Max Ref 0 to 65 60 MAXREF
ACCL IDF VFD Accel. Time 1 to 1800 10 RAMPUP_T
DECL IDF VFD Decel. Time 1 to 1800 10 RAMPDN_T
MAX.A IDF VFD Max Current 0 to 655.35
See VFD Motor Default
Configuration Tables.
Table 35 (sizes 04-06)
Table 42 (Vert. sizes
07-26)
Table 43 (Horz. Sizes
14-26)
VFD1MAXA
F.TO IDF Danfoss Comm. TO 1 to 600 30 CNT_TOUT
R.TIM IDF Danfoss Auto Reset 0 to 600 30 ARSTRT_T
RFI IDF Danfoss RFI Filter On/Off On RFIFILTR
ECON Economizer Config Menu
EC.EN Economizer Installed? Yes/No
No: no FIOP
Yes: FIOP
ECONO
EC.MX Econ Max Damper Position 0-100 % 100 DAMPMAX
FC.MX Free Cooling Max OAT 0 to 90 °F 65 MAXFREET
E.TRV Economizer Travel Time 5 to 300 sec 150 ECONOTRV
MIN.P Min Position Config Menu
MP.MX Econ Min at Max Fanspeed 0-100 % 30 MINP_MAX
MP.S1 Min Pos - User Speed 1 0-100 % 0 MP_USPD1
MP.D1 Min Pos - User Pos 1 0-100 % 0 MP_UPOS1
MP.S2 Min Pos - User Speed 2 0-100 % 0 MP_USPD2
MP.D2 Min Pos - User Pos 2 0-100 % 0 MP_UPOS2
MP.S3 Min Pos - User Speed 3 0-100 % 0 MP_USPD3
MP.D3 Min Pos - User Pos 3 0-100 % 0 MP_UPOS3
NET Building Net Config Menu
BAS BAS Protocol Select
0=NONE,
1=CCN,
2=BACNET
0=NONE BMS_CFG
NW.TO Network Input Timeout 0 to 600 min 30 NETINTO
CCN CCN Network Config Menu
CCN.B CCN Bus Number 0 to 239 0 CCNBUS
CCN.A CCN Element Number 1 to 239 1 CCNADD
BAUD CCN Baud Rate
0=9600,
1=19200,
2=38400
2 BAUDENUM
BNET BACnet Config Menu
MAC BACnet Device Macaddress 1 to 127 01 BAC_MAC
BAUD BACnet BMS Baud Rate
0=9600,
1=19200,
2=38400,
3=57600,
4=76800,
5=115200
4=76800 BAC_BAUD
AUID ALC Auto Id Scheme Yes/No Yes AUID
Table O — MODE – CONFIGURATIONS (cont)
ITEM EXPANSION RANGE UNIT DEFAULT POINT
APPENDIX C — NAVIGATOR™ DISPLAY