Table U — SERVICE CONFIGURATION TABLES
TABLE NAME DISPLAY NAME RANGE UNITS POINT NAME DEFAULT
TOUCH
Equip Sys Touch Active enum ETST_ACT
Equipment Touch SPT °F ETSPT
Equipment Touch RH % ETSPRH
System Touch Temp Value °F STST_NET
System Touch SPRH Value % STRH_NET
ET ST Aggregated SPT °F ETSTSPT
ET ST Aggregated SPRH % ETSTSPRH
UNIT_CFG
Unit Startup Delay 10 to 600 sec STARTDLY 30
Auxiliary Vent Type 1 VENTTYPE
Unit Control Type
0 = Thermostat,
1 = Space Sensor,
2 = RAT Control
CTRLTYPE 0=TSTAT
Thermostat Hardware Type
0 = 2 Stage Conventional,
1 = 2 Stage Digital,
2 = 3 Stage Conventional,
3 = 3 Stage Digital
STATTYPE 2=CONV 3C2H
Tstat Adaptive Staging Yes/No ADPTSTAT Yes
Change Filter Timer 0 to 9999 hours FILTLIFE 600
Test Inactivity Time Out
0 =Disabled,
1 = 30 Minutes,
2 = 1 Hour,
3 = 2 Hours,
4 = 4 Hours,
5 = 8 Hours,
6 = 12 Hours
TEST_ITO 4=4 hours
CCH Max Temperature 40 to 90 °F CCHMAXT 65
Std Barometric Pressure 13 to 35 in. Hg STD_BARP 29.92
Linkage Stage Inc. Time 60 to 600 sec LSTAGINC 180
Unit’s Maximum SAT 130 to 210 °F UMAX_SAT 200
Auto Clr SAT Limit Fault Yes/No SATLACLR No
Adaptive Temp Comp Start Enable/Disable TCS_CFG Enable
User TCS Start Bias Time 0 to 180 min TCSUBIAS 0
SIOB 1 Enabled Yes/No SIOB1_EN
DMD_CFG
Low Cool Demand On –1 to 2 °F DMDLCON 0.5
Medium Cool Demand On 0.5 to 20 °F DMDMCON 1
High Cool Demand On 0.5 to 20 °F DMDHCON 2
Low Cool Demand Off –1 to 2 °F DMDLCOFF –0.5
Cool Demand Level Up –2 to 2 ^F/min CDMD_LUP –0.2
Low Heat Demand On 1 to 2 °F DMDLHON 0.5
High Heat Demand On 0.5 to 20 °F DMDHHON 2
Low Heat Demand Off 1 to 2 °F DMDLHOFF –0.5
Heat Demand Level Up –2 to 2 ^F/min HDMD_LUP –0.2
Space Demand Time Guard 1 60 to 600 sec TDMD_TG1 180
Space Demand Time Guard 2 0 to 600 sec TDMD_TG2 300
Space Demand Time Guard 3 5 to 120 min TDMD_TG3 10
COOL DMD Offset Level 1 0 to 99 °F CLDOLEV1
COOL DMD Offset Level 2 0 to 99 °F CLDOLEV2
COOL DMD Offset Level 3 0 to 99 °F CLDOLEV3
Heat DMD Offset Level 1 0 to 99 °F HTDOLEV1
Heat DMD Offset Level 2 0 to 99 °F HTDOLEV2
Heat DMD Offset Level 3 0 to 99 °F HTDOLEV3
INPUTCFG Humidistat Status Channel
0 =None,
1 = MBB DI12,
2 = MBB DI13,
3 = MBB DI14,
4 = MBB DI02,
5 = MBB DI04,
6 = SIOB DI01
HUMDCHAN