164
OA Quality Level R/W PPM oaq AV:1012 0 to 5000 OAQ
OA Relative Humidity R/W % oarh AV:1022 0 to 1 OARH
OACFM Assigned Channel R/W ocfmchan AV:370 0 to 3 OCFMCHAN
OACFM at 4MA R/W CFM ocfm_4ma AV:369 0 to 5000 OCFM_4MA
OACFM Value at 20mA R/W CFM ocfm20ma AV:417 0 to 5000 OCFM20MA
OAQ Assigned Channel R/W oaq_channel AV:426 0 to 3 OAQ_CHAN
OARH Assigned Channel R/W oarh_channel AV:23 0 to 3 OARHCHAN
OARH Sensor Val. at 20mA R/W % oarh_20ma AV:22 0.6 to 1.0 OARH20MA
OARH Sensor Value at 4mA R/W % oarh_4ma AV:21 0 to 0.5 OARH_4MA
OATLimitForSupAirTemp R/W °F oatstemp AV:424 –40 to 125 OATSTEMP
Object instance for IAQ R/W objiaq AV:8008 0 to 9999 OBJIAQ
Object instance for OAQ R/W objoaq AV:8009 0 to 9999 OBJOAQ
Object instance for OARH R/W objoarh AV:8011 0 to 9999 OBJOARH
Object instance for OAT R/W objoat AV:8010 0 to 9999 OBJOAT
Object instance for RARH R/W objrarh AV:8012 0 to 9999 OBJRARH
Object instance for RAT R/W objrat AV:8013 0 to 9999 OBJRAT
Object instance for SPRH R/W objsprh AV:8029 0 to 9999 OBJSPRH
Object instance for SPT R/W objspt AV:8014 0 to 9999 OBJSPT
Occ Cooling Required READ ONLY °F lnk_ocrq AV:263 0 to 30 LNK_OCRQ
Occ Heating required READ ONLY °F lnk_ohrq AV:265 0 to 30 LNK_OHRQ
Occupied Cool Setpoint R/W °F ocsp AV:288 55 to 80 OCSP
Occupied Heat Setpoint R/W °F ohsp AV:289 55 to 80 OHSP
Occupied Setpoint Gap R/W odb AV:6003 0 to 10 ODB
Occupied SPRH Setpoint READ ONLY % sprh_osp AV:367 0.10 to 1 SPRH_OSP
Occupied Zone Setpoint R/W °F osp AV:6002 40 to 80 OSP
ODF Control SDT SP READ ONLY 'F odfsdtsp AV:433 –100 to 500 ODFSDTSP
ODF High Cool Speed R/W RPM odf_hi_speed AV:82 0 to 1200 ODFHCSPD
ODF High Speed Time R/W sec minodftm AV:280 0 to 300 MINODFTM
ODF Low Cool Speed R/W RPM odf_lo_speed AV:83 0 to 1200 ODFLCSPD
ODF Maximum Speed R/W RPM odf_max_speed AV:86 0 to 1200 ODFMAXSP
ODF Med Cool Speed R/W RPM odf_med_speed AV:84 0 to 1200 ODFMCSPD
ODF Minimum Speed R/W RPM odf_min_speed AV:85 0 to 1200 ODFMINSP
ODF Signal1 Resets Count READ ONLY rs_odf1 AV:110 0 to 65535 RS_ODF1
ODF Signal2 Resets Count READ ONLY rs_odf2 AV:111 0 to 65535 RS_ODF2
ODF Signal3 Resets Count READ ONLY rs_odf3 AV:112 0 to 65535 RS_ODF3
ODF Spd Sig 1 Run Hours READ ONLY hrs hour_odf1 AV:58 0 to 999999 HR_ODF1
ODF Spd Sig 2 Run Hours READ ONLY hrs hour_odf2 AV:59 0 to 999999 HR_ODF2
ODF Spd Sig 3 Run Hours READ ONLY hrs hour_odf3 AV:60 0 to 999999 HR_ODF3
ODF Spd Signal 1 Starts READ ONLY st_odf1 AV:302 0 to 999999 ST_ODF1
ODF Spd Signal 2 Starts READ ONLY st_odf2 AV:146 0 to 999999 ST_ODF2
ODF Spd Signal 3 Starts READ ONLY st_odf3 AV:147 0 to 999999 ST_ODF3
ODF Speed Signal Output1 READ ONLY RPM odf1_rpm AV:26 0 to 1200 ODF1SPD
ODF Speed Signal Output2 READ ONLY RPM odf2_rpm AV:27 0 to 1200 ODF2SPD
ODF Speed Signal Output3 READ ONLY RPM odf3_rpm AV:28 0 to 1200 ODF3SPD
Outdoor Air Enthalpy R/W BTU_LB oa_enth AV:76 –9.6f to 334.2f OA_ENTH
outdoor Air in CFM R/W CFM oacfm AV:416 0 to 5000 OACFM
Outdoor Air Temp Sensor READ ONLY °F oat_loc AV:286 –40 to 245 OAT_LOC
Outdoor Air Temperature R/W °F oa_temp AV:1003 –40 to 245 OAT
Outdoor Fan 1 speed test R/W RPM s_odfsp1 AV:120 0 to 1200 S_ODFSP1
Outdoor Fan 2 speed test R/W RPM s_odfsp2 AV:121 0 to 1200 S_ODFSP2
Outdoor Fan 3 speed test
R/W RPM s_odfsp3 AV:122 0 to 1200 S_ODFSP3
P.Exhaust 1 Curve Offset READ ONLY % pe1_offs AV:317 0 to 1 PE1_OFFS
P.Exhaust 1 Resets Count READ ONLY rs_pe_1 AV:113 0 to 65535 RS_PE_1
P.Exhaust 2 Curve Offset READ ONLY % pe2_offs AV:229 0 to 1 PE2_OFFS
P.Exhaust 2 Resets Count READ ONLY rs_pe_2 AV:114 0 to 65535 RS_PE_2
PE Stage 1 At Max Speed R/W % pe1_pmax AV:343 0 to 1 PE1_PMAX
PE Stage 2 At Max Speed R/W % pe2_pmax AV:344 0 to 1 PE2_PMAX
PE Turn Off Dead band R/W % pe_offdb AV:316 0 to 1 PE_OFFDB
PE1 Assigned Relay R/W pe1_channel AV:365 0 to 2 PE1_CHAN
PE2 Assigned Relay R/W pe2_channel AV:366 0 to 2 PE2_CHAN
Pilot Space Temp Value R/W °F space_temp AV:2007 –40 to 245 SPT
Table Y — BACnet* AV Points List (cont)
POINT DESCRIPTION POINT ACCESS UNITS
BACNET
OBJECT NAME
BACNET
ID
VALUE
RANGE
CCN POINT
EQUIVALENT
APPENDIX E — BACNET POINTS LIST