174
MODEL NO._______________________________________
SERIAL NO._______________________________________
DATE_____________________________________________
TECHNICIAN______________________________________
SOFTWARE VERSIONS:
MBB:CESR131651–_________________________________
VFD FW VERSION–________________________________
INDICATE UNIT SETTINGS BELOW
CONTROL TYPE: Thermostat/T55 Space Temp./T-56 Space Temp./T-59 Space Temp.
SETPOINT Cooling Occupied:_________________ Unoccupied:_______________
Heating Occupied:_________________ Unoccupied:_______________
Table AC — Settings Main Menu Layout
DISPLAY TEXT EXPANDED TEXT RANGE UNITS DEFAULT POINT ENTRY
SETTINGS Settings Menu
SPACE SET POINTS
Space Setpoints Adjustment
Menu
OCC COOL SETPOINT Occupied Cool Setpoint 55 to 80 °F 78 OCSP
OCC HEAT SETPOINT Occupied Heat Setpoint 55 to 80 °F 68 OHSP
UNOCC COOL SETPNT Unoccupied Cool Setpoint 65 to 95 °F 85 UCSP
UNOCC HEAT SETPNT Unoccupied Heat Setpoint 40 to 80 °F 60 UHSP
HEAT-COOL SP GAP Heat-Cool Setpoint Gap 2 to 10 ^F 5 HCSP_GAP
SPT SLIDER RANGE SPT Offset Range (±) 0 to 5.0 °F 5 SPTO_RNG
OCC SPRH SET PT Occupied SPRH Setpoint 0 to 100 % 55 SPRH_OSP
UNOCC SPRH SET PT Unoccupied SPRH Setpoint 0 to 100 % 55 SPRH_USP
SA TEMPER SET PNT SA Tempering Setpoint xx °F 50 SATEMPSP
TEMP DEMAND CONFIG
Temperature Demand
Configuration Menu
LOW COOL DMD ON Low Cool Demand On –1 to 2.0 °F 0.5 DMDLCON
MED COOL DMD ON Medium Cool Demand On 0.5 to 20.0 °F 1 DMDMCON
HIGH COOL DMD ON High Cool Demand On 0.5 to 20.0 °F 2 DMDHCON
LOW COOL DMD OFF Low Cool Demand Off –1 to 2.0 °F –0.5 DMDLCOFF
COOL DMD LEVEL UP Cool Demand Level Up –2 to 2.0 ^F/min –0.2 CDMD_LUP
LOW HEAT DMD ON Low Heat Demand On –1 to 2.0 °F 0.5 DMDLHON
HIGH HEAT DMD ON High Heat Demand On 0.5 to 20.0 °F 2 DMDHHON
LOW HEAT DMD OFF Low Heat Demand Off –1 to 2.0 °F –0.5 DMDLHOFF
HEAT DMD LEVEL UP Heat Demand Level Up –2 to 2.0 ^F/min –0.2 HDMD_LUP
DEMAND TIMEGUARD1 Space Demand Time Guard1 60 to 600 sec 180 TDMD_TG1
DEMAND TIMEGUARD2 Space Demand Time Guard2 0 to 600 sec 300 TDMD_TG2
DEMAND TIMEGUARD3 Space Demand Time Guard3 5 to 120 min 10 TDMD_TG3
DMD LIMIT CONFIG DEMAND LIMIT CONFIG
COOL DMD LIM LEV1 Cool DMD Offset level 1 0 to 99 °F 1 CLDOLEV1
COOL DMD LIM LEV2 Cool DMD Offset level 2 0 to 99 °F 3 CLDOLEV2
COOL DMD LIM LEV3 Cool DMD Offset level 3 0 to 99 °F 5 CLDOLEV3
HEAT DMD LIM LEV1 Heat DMD Offset level 1 0 to 99 °F 1 HTDOLEV1
HEAT DMD LIM LEV2 Heat DMD Offset level 2 0 to 99 °F 3 HTDOLEV2
HEAT DMD LIM LEV3 Heat DMD Offset level 3 0 to 99 °F 5 HTDOLEV3
CLOCK Clock Adjustment Menu
TIME Clock Hour and Minute xx:xx hh.mm TIME
DATE Current Date MM/DD/YYYY DATE
DAYLIGHT SAVINGS
Daylight Savings
Configuration Menu
DST Menu
DAYLIGHT SAVINGS? DST allowed? Enable/Disable Enable DST_CFG
CONTROL SET POINT AND CONFIGURATION LOG