186
NETWORK SETTINGS (cont)
OBJECT ID OAT Object instance for OAT 0 to 9999 1003 OBJOAT
COV OAT Change of value for OAT 0 to 60 0 COVOAT
DEVICE RARH BACnet device for RARH 0 to 4194303 1610100 DEVRARH
OBJECT ID RARH Object instance for RARH 0 to 9999 30 OBJRARH
COV RARH Change of value for RARH 0 to 60 0 COVRARH
DEVICE RAT BACnet device for RAT 0 to 4194303 1610100 DEVRAT
OBJECT ID RAT Object instance for RAT 0 to 9999 1010 OBJRAT
COV RAT Change of value for RAT 0 to 60 0 COVRAT
DEVICE SPT BACnet device for SPT 0 to 4194303 1610100 DEVSPT
OBJECT ID SPT Object instance for SPT 0 to 9999 2007 OBJSPT
COV SPT Change of value for SPT 0 to 60 0 COVSPT
LOCAL_SHEDL_EDIT Allow Local Sched Edit Yes/No enum No LCL_EDIT
SYSTEM TOUCH System Touch Menu
DEVICE INSTANCE System Touch Device Inst 0 to 4194303 160099 DEVST
POLLING RATE System Touch Poll Rate 10 to 60 10 POLLST
SPACE TEMP AI System Touch AI for SPT 0 to 9999 1 AISTSPT
SPACE RH AI System Touch AI for SPRH 0 to 9999 4 AISTSPRH
ZS SENSOR CFG ZS Sensor Configuration
ZS1 ADDRESS Zone Sensor 1 Address 0 to 255 255 ZSADDR1
ZS2 ADDRESS Zone Sensor 2 Address 0 to 255 255 ZSADDR2
ZS3 ADDRESS Zone Sensor 3 Address 0 to 255 255 ZSADDR3
ZS4 ADDRESS Zone Sensor 4 Address 0 to 255 255 ZSADDR4
ZS5 ADDRESS Zone Sensor 5 Address 0 to 255 255 ZSADDR5
ZS POLL RATE Zone Sensor Poll Rate 1 to 100 sec 5 ZSPOLLRT
ZS UNIT Zone Sensor Unit 0=degrees F 0=degrees F ZSUNIT
ZS FRC UNOC ENBL ZS Force Unoccup Enable No No ZSFUNEN
ZS FRC UNOC DELAY ZS Force Unocc wt Delay No No ZSFUNWT
ZS TLO CONT ENBL ZS TLO Cont Enable No No ZSTLOEN
TLO SET DURING OC ZS TLO set during occ No No ZSTLSOC
ZS UI MODE Zone sensor UI Mode 1=Dual Offsets 1=Dual Offsets ZSUIM
NETWORK CHKLIST
NETWORK SETUP
CHECKLIST
0=Undone,
1=Perfom,
2=Done
0=Undone CHK_NET
DISPLAY SETTINGS
User Display Configurations
Menu
METRIC DISPLAY Metric Display Yes/No No DISPUNIT
LANGUAGE Display Language Select 0=English 0=English LANGUAGE
CONTRAST ADJUST LCD Contrast Adjustment 1 to 10 5 LCD_CONT
PASSWORD ENABLE? User Password Protection Enable/Disable Enable PASS_EBL
VIEW USER PASSWORD View User Password Menu
CHANGE USER PASSWORD Change User Password Menu
QUICK SETUP CONFIG
QUICK SETUP CONFIG
MENU
TIME Clock Hour and Minute xx:xx hh.mm 0 TIME
DATE Current Date MM/DD/YYYY 0 DATE
STARTUP DELAY Unit Startup Delay 10 to 600 sec 30 STARTDLY
UNIT CONTROL TYPE Unit Control Type
0=TSTAT,
1=SPACE SEN,
2=RAT SEN
0=TSTAT CTRLTYPE
THERMOSTAT TYPE Thermostat Hardware Type
0=CONV 2C2H,
1=DIGI 2C2H,
2=CONV 3C2H,
3=DIGI 3C2H
4=DIGI 2C2H
2=CONV 3C2H STATTYPE
DIRTY FILTER TIME Change Filter Timer 0 to 9999 hours 600 FILTLIFE
VENT IDF SPEED Ventilation Only IDF Spd 0 to 100 %
50 (sizes 04-06)
67 (sizes 07-12)
53 (sizes 14 or
20)
56 (size 17)
52 (size 24)
60 (size 26)
FSPDVENT
Table AC — Settings Main Menu Layout (cont)
DISPLAY TEXT EXPANDED TEXT RANGE UNITS DEFAULT POINT ENTRY
CONTROL SET POINT AND CONFIGURATION LOG