EasyManua.ls Logo

Carrier 48NLT - Start-Up

Carrier 48NLT
27 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SPECIAL
PROCEDURES
FOR
208-V
OPERATION
A
WARNING
Make
sure
that
the
power
supply
to
the
unit
is
switched
OFF
before
making
any
wiring
changes.
Electrical
shock
can
cause
pers
onal
injury
or
death.
_
1.
Disconnect
the
orange
transformer-primary
lead
from
the
contactor.
See
unit
wiring
label.
2.
Remove
the
tape
and
cover
from
the
terminal
on
the
end
of
the
red
transformer-primary
lead.
3.
Save
the
cover.
4.
Connect
the
red
lead
to
the
contactor
terminal
from
which
the
orange
lead
was
disconnected.
5.
Using
the
cover
removed
from
the
red
lead,
insulate
the
loose
terminal
on
the
orange
lead.
6.
Wrap
the
cover
with
electrical
tape
so
that
the
metal
ter¬
minal
cannot
be
seen.
Indoor
blower
motor
speeds
should
be
changed
for
208-v
operation.
In
the
unit
control
box,
change
motor
leads
on
the
printed
circuit
board
so
that
high
speed
is
used
for
cool¬
ing
and
medium
speed
is
used
for
heating.
Do
not
change
blower
speed
setting
for
460-v
rated
units.
Refer
to
Start-
Up,
Indoor
Airflow
and
Airflow
Adjustments
section.
CONTROL
VOLTAGE
CONNECTIONS
Locate
the
room
thermostat
on
an
inside
wall
in
the
space
to
be
conditioned,
where
it
will
not
be
subjected
to
either
a
cooling
or
heating
source
or
direct
exposure
to
sunlight.
Mount
the
thermostat
4
to
5
ft
above
the
floor.
Use
no.
18
American
Wire
Gage
(AWG)
color-coded,
insulated
(35
C
minimum)
wires
to
make
the
control
volt¬
age
connections
between
the
thermostat
and
the
unit.
If
the
thermostat
is
located
more
than
100
ft
from
the
unit
(as
measured
along
the
control
voltage
wires),
use
no.
16
AWG
color-coded,
insulated
(35
C
minimum)
wires.
A
grommeted,
control
voltage
inlet
hole
is
located
in
the
panel
adjacent
to
the
control
access
panel.
Run
the
low-
voltage
leads
from
the
thermostat,
through
the
inlet
hole,
and
to
the
control
voltage
terminals
through
a
hole
in
the
bottom
of
the
unit
control
box.
Pass
control
voltage
leads
through
wire
ties
located
under
unit
control
box.
Connect
the
thermostat
leads
to
the
terminals
as
shown
in
Fig.
10.
HEAT
ANTICIPATOR
SETTING
-
The
room
thermostat
heat
anticipator
must
be
adjusted
properly
to
ensure
proper
heating
performance.
Set
the
heat
anticipator,
using
an
THERMOSTAT
(TYPICAL)
T
ERMINAL
BOARD
CONTROL
BOX
rti
GND
CONTACTOR
TERMINALS
(SEE
UNIT
WIRING
LABEL)
POWER
SUPPLY
FIELD
SUPPLIED
FUSED
DISCONNECT
p/“‘
z..
1
p"
i
1
—1
3-PHASE
UNITS
ONLY
-FIELD
CONTROL-VOLTAGE
WIRING
FIELD
HIGH-VOLTAGE
WIRING
Fig.
10
High-
and
Control-Voltage
Connections
ammeter
between
the
W
and
R
terminals
to
determine
the
exact
required
setting.
NOTE:
For
thermostat
selection
purposes,
use
0.6
amp
for
the
approximate
required
setting.
Failure
to
make
a
proper
heat
anticipator
adjustment
will
result
in
improper
operation,
discomfort
to
the
occupants
of
the
conditioned
space
and
inefficient
energy
utilization;
however,
the
required
setting
may
be
changed
slightly
to
provide
a
greater
degree
of
comfort
for
a
particular
installation.
TRANSFORMER
CIRCUIT
PROTECTION
-
The
unit
transformer
contains
an
auto,
reset
overcurrent
protector
for
control
circuit
protection.
If
this
device
trips,
it
may
reset
without
warning,
starting
the
heating
or
cooling
section
of
this
product.
Use
caution
when
servicing;
if
overcurrent
protector
continues
to
trip,
there
is
a
problem
in
the
low-
voltage
electrical
circuit,
such
as
an
electrical
short,
ground
or
transformer
overload.
Disconnect
power,
correct
the
con¬
dition,
and
check
for
normal
unit
operation.
PRE-START-UP
A
WARNING
Failure
to
observe
the
following
warnings
could
result
in
serious
personal
injury:
1.
Follow
recognized
safety
practices
and
wear
protec¬
tive
goggles
when
checking
or
servicing
refrigerant
system.
2.
Do
not
operate
compressor
or
provide
any
electric
power
to
unit
unless
compressor
terminal
cover
is
in
place
and
secured.
3.
Do
not
remove
compressor
terminal
cover
until
all
electrical
sources
are
disconnected.
4.
Relieve
all
pressure
from
system
before
touching
or
disturbing
anything
inside
terminal
box
if
refriger¬
ant
leak
is
suspected
around
compressor
terminals.
5.
Never
attempt
to
repair
soldered
connection
while
refrigerant
system
is
under
pressure.
6.
Do
not
use
torch
to
remove
any
component.
System
contains
oil
and
refrigerant
under
pressure.
To
re¬
move
a
component,
wear
protective
goggles
and
pro¬
ceed
as
follows:
a.
Shut
off
gas
supply
and
then
electrical
power
to
unit.
b.
Relieve
all
pressure
from
system
using
both
high-
and
low-pressure
ports.
c.
Cut
component
connecting
tubing
with
tubing
cut¬
ter
and
remove
component
from
unit.
d.
Carefully
unsweat
remaining
tubing
stubs
when
necessary.
Oil
can
ignite
when
exposed
to
torch
flame.
Proceed
as
follows
to
inspect
and
prepare
the
unit
for
ini¬
tial
start-up:
1.
Remove
all
access
panels.
2.
Read
and
follow
instructions
on
all
WARNING,
CAU¬
TION
and
INFORMATION
labels
attached
to,
or
shipped
with,
unit.
Make
the
following
inspections:
a.
Inspect
for
shipping
and
handling
damages
such
as
broken
lines,
loose
parts,
disconnected
wires,
etc.
b.
Inspect
for
oil
at
all
refrigerant
tubing
connections
and
on
unit
base.
Detecting
oil
generally
indicates
10

Related product manuals