EasyManua.ls Logo

Carrier 48NLT - Page 12

Carrier 48NLT
27 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table
4
Rated
Gas
Inputs
UNIT
48
NUMBER
OF
ORIFICES
GAS
SUPPLY
PRESSURE
(in.
wg)
MANIFOLD
PRESSURE
(in.
wg)
NATURAL
GAS
PROPANE*
Natural
Propane
Orifice
Drill
Size
Heating
Input
(Btuh)t
Orifice
Drill
Size
Heating
Input
(Btuh)t
Min
Max
Min
Max
Natural
Propane
NLT018,024,030
2
5.0
13.6
11
0
136
35
10.5
44
40,000
55
40,000
NLT036,042;
NHT024;
NMT030
3
50
13.6
11.0
13,6
3.5
10.5
44
60,000
55
60,000
NLT048,060;
NMT036,042;
NHT030
4
5.0
13.6
11.0
13.6
3.5
105
44
80,000
55
80,000
NET036,042
4
5.0
136
11
0
13,6
3.5
10.5
42
96,000
54
96,000
NMT048,060;
NHT036,042
5
5.0
13.6
11.0
13.6
3.5
10.5
44
100,000
55
100,000
NHT048,060;
NVT036,042
6
5.0
13.6
11.0
13.6
35
10.5
44
-
-
1
120,000
55
120,000
NVT048,060
6
50
13.6
11.0
136
3.5
10.5
42
,
144,000
54
144,000
*When
a
48N
unit
is
converted
to
propane,
the
unit
must
be
modified.
See
kit
instructions.
tBased
on
altitudes
from
sea
level
up
to
2000
ft
above
sea
level.
For
altitudes
above
2000
ft,
reduce
input
rating
4%
for
each
1000
ft
above
sea
level
In
Canada,
from
2000
ft
above
sea
level
to
4500
ft
above
sea
level,
derate
the
unit
10%,
NOTE;
All
other
appliances
that
use
the
same
meter
must
be
turned
off
when
gas
flow
is
measured
at
the
meter.
Proceed
as
follows:
1.
Turn
off
gas
supply
to
unit.
2.
Remove
pipe
plug
on
outlet
of
gas
valve,
then
connect
manometer
at
this
point.
Turn
on
gas
to
unit.
3.
Record
number
of
seconds
for
gas
meter
test
dial
to
make
one
revolution.
4.
Divide
number
of
seconds
in
Step
3
into
3600
(number
of
seconds
in
one
hour).
5.
Multiply
result
of
Step
4
by
the
number
of
cu
ft
shown
for
one
revolution
of
test
dial
to
obtain
cu
ft
of
gas
flow
per
hour.
6.
Multiply
result
of
Step
5
by
Btu
heating
value
of
gas
to
obtain
total
measured
input
in
Btuh.
Compare
this
value
with
heating
input
shown
in
Table
4.
(Consult
the
local
gas
supplier
if
the
heating
value
of
gas
is
not
known.)
Example:
Assume
that
the
size
of
test
dial
is
one
cu
ft,
one
revolution
takes
30
seconds,
and
the
heating
value
of
the
gas
is
1050
Btu/ft^.
Proceed
as
follows:
1.
30
seconds
to
complete
one
revolution.
2.
3600
^
30
=
120.
3.
120
X
1
=
120
ft^
of
gas
flow/hr.
4.
120
X
1050
=
126,000
Btuh
input.
If
the
desired
gas
input
is
125,000
Btuh,
only
a
minor
change
in
the
manifold
pressure
is
required.
Observe
manifold
pressure
and
proceed
as
follows
to
adjust
gas
input:
1.
Remove
cover
screw
over
regulator
adjustment
screw
on
gas
valve.
2.
Turn
regulator
adjustment
screw
clockwise
to
increase
gas
input,
or
turn
regulator
adjustment
screw
counter¬
clockwise
to
decrease
input.
Manifold
pressure
must
be
between
3.2
and
3.8
in.
wg.
A
WARNING
Unsafe
operation
of
the
unit
may
result
if
manifold
pressure
is
outside
this
range.
Personal
injury
or
unit
damage
may
result.
3.
Replace
cover
screw
cap
on
gas
valve.
4.
Turn
off
gas
supply
to
unit.
Remove
manometer
from
pressure
tap.
Replace
pipe
plug
on
gas
valve.
Turn
on
gas
to
unit.
Check
for
leaks.
Measure
Manifold
Pressure
(Propane
Units)
The
main
burner
orifices
on
a
propane
gas
unit
are
sized
for
the
unit
rated
input
when
the
manifold
pressure
is
10.5
in.
wg.
Proceed
as
follows
to
adjust
gas
input
on
a
propane
gas
unit:
1.
Turn
off
gas
to
unit.
2.
Remove
pipe
plug
on
outlet
of
gas
valve,
then
connect
manometer
at
this
point.
3.
Turn
on
gas
to
unit.
4.
Remove
cover
screw
over
regulator
adjustment
screw
on
gas
valve.
5.
Adjust
regulator
adjustment
screw
for
a
manifold
pres¬
sure
reading
of
10.5
in.
wg.
Turn
adjusting
screw
clock¬
wise
to
increase
manifold
pressure,
or
turn
adjusting
screw
counterclockwise
to
decrease
manifold
pressure.
6.
Replace
cover
screw.
7.
Turn
off
gas
to
unit.
Remove
manometer
from
pressure
tap.
Replace
pipe
plug
on
gas
valve,
then
turn
on
gas
to
unit.
Check
for
leaks.
CHECK
BURNER
FLAME
Observe
the
unit
heating
operation,
and
watch
the
burner
flames
through
the
obser¬
vation
port
to
see
if
they
are
light
blue
and
soft
in
appear¬
ance,
and
that
the
flames
are
approximately
the
same
for
each
burner.
See
Fig.
11.
BLOWER
HEAT-RELAY
OPERATION
-
Blower
relay
PCI
(see
the
unit
wiring
diagram)
is
located
in
the
control
box
and
adjusts
to
permit
either
longer
or
shorter
“off”
cy¬
cles.
The
“on”
cycle
is
factory
set
for
one
minute
on
tim¬
ing.
The
adjusting
dial
on
the
relay
(see
Fig.
12)
is
factory
set
at
the
minimum
position
to
provide
optimum
perfor¬
mance
for
most
installations.
On
unusual
installations,
the
length
of
time
the
blower
remains
on
may
need
to
be
increased.
To
increase
blower
operation
time,
rotate
the
ad¬
justing
dial
counterclockwise.
To
decrease
blower
opera¬
tion
time,
rotate
dial
clockwise.
AIRFLOW
AND
TEMPERATURE
RISE
-
The
heating
section
for
each
size
unit
is
designed
and
approved
for
heat¬
ing
operation
within
the
temperature-rise
range
stamped
on
the
unit
rating
plate.
Table
5
shows
the
approved
temperature-rise
range
for
each
unit,
and
the
air
delivery
cfm
at
various
temperature
rises.
The
heating
operation
airflow
must
produce
a
tem¬
perature
rise
that
falls
within
the
approved
range.
Refer
to
Indoor
Airflow
and
Airflow
Adjustments
sec¬
tion
to
adjust
heating
airflow
when
required.
12

Related product manuals