EasyManua.ls Logo

Carrier 48NLT - Page 25

Carrier 48NLT
27 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Condenser
Fan
A
CAUTION
Keep
the
condenser
fan
free
from
all
obstructions
to
ensure
proper
cooling
operation.
Never
place
articles
on
top
of
the
unit.
Damage
to
unit
may
result._
Remove
control
and
compressor
access
panels.
Inspect
the
fan
blades
for
cracks
or
bends
each
year.
Make
sure
that
blades
clear
the
motor
by
no
more
than
V4
inch.
If
the
blade
assembly
has
slipped
down
the
motor
shaft,
adjust
the
fan
position
on
the
motor
shaft
by
loosening
the
set-
sere
w(s),
then
moving
the
blade
assembly
up.
Be
sure
that
the
setscrew(s)
is
on
the
flat(s)
of
the
motor
shaft
before
tightening.
Electrical
Controls
and
Wiring
Inspect
and
check
the
electrical
controls
and
wiring
annually.
Be
sure
to
turn
off
the
gas
supply,
and
then
the
electrical
power
to
the
unit.
Remove
the
control,
blower
and
compressor
compart¬
ment
access
panels
to
locate
all
the
electrical
controls
and
wiring.
Check
all
electrical
connections
for
tightness.
Tighten
all
screw
connections.
If
any
smoky
or
burned
connections
are
noticed,
disassemble
the
connection,
clean
all
the
parts,
restrip
the
wire
end
and
reassemble
the
connection
properly
and
securely.
After
inspecting
the
electrical
controls
and
wiring,
re¬
place
all
the
panels.
Start
the
unit,
and
observe
at
least
one
complete
heating
cycle
and
one
complete
cooling
cycle
to
ensure
proper
operation.
If
discrepancies
are
observed
in
either
or
both
operating
cycles,
or
if
a
suspected
malfunc¬
tion
has
occurred,
check
each
electrical
component
with
the
proper
electrical
instrumentation.
Refer
to
the
unit
wiring
label
when
making
these
checkouts.
NOTE:
Refer
to
the
heating
and/or
cooling
sequence
of
op¬
eration
in
this
publication
as
an
aid
in
determining
proper
control
operation.
RGfrigerant
Circuit
Inspect
all
refrigerant
tubing
con¬
nections
and
the
unit
base
for
oil
accumulations
annually.
Detecting
oil
generally
indicates
a
refrigerant
leak.
If
oil
is
detected
or
if
low
cooling
performance
is
sus¬
pected,
leak-test
all
refrigerant
tubing
using
an
electronic
leak-detector,
or
liquid-soap
solution.
If
a
refrigerant
leak
is
detected,
refer
to
Start-Up,
Check
for
Refrigerant
Leaks
section.
If
no
refrigerant
leaks
are
found
and
low
cooling
perfor¬
mance
is
suspected,
refer
to
Checking
and
Adjusting
Re¬
frigerant
Charge
section.
Gas
Input
The
gas
input
does
not
require
checking
unless
improper
heating
performance
is
suspected.
If
a
prob¬
lem
exists,
refer
to
Start-Up
section.
Evaporator
Airflow
The
heating
and/or
cooling
air¬
flow
does
not
require
checking
unless
improper
perfor¬
mance
is
suspected.
If
a
problem
exists,
be
sure
that
all
supply-
and
return-air
grilles
are
open
and
free
from
ob¬
structions,
and
that
the
air
filter
is
clean.
When
necessary,
refer
to
Indoor
Airflow
and
Airflow
Adjustment
section
to
check
the
system
airflow.
Metering
Device
Servicing
See
Fig.
16
for
me¬
tering
device
components.
The
piston
has
a
refrigerant
me¬
tering
orifice
through
it.
The
retainer
forms
a
sealing
sur¬
face
for
liquid
line
flare
connection.
To
check,
clean
or
replace
piston:
1.
Shut
off
power
to
unit.
2.
Remove
refrigerant
from
unit
using
approved
refrigerant
removal
methods
from
both
high-
and
low-service
port
connections.
3.
Remove
liquid
line
flare
connections
from
metering
device.
4.
Note
position
of
arrow
on
metering
device
body
with
respect
to
unit.
5.
Pull
retainer
out
of
body.
Be
careful
not
to
scratch
flare
sealing
surface.
If
retainer
does
not
pull
out
easily,
care¬
fully
use
locking
pliers
to
remove
retainer.
Replace
scratched
or
damaged
retainer.
6.
Slide
piston
out
by
inserting
a
small,
soft
wire
through
metering
hole
(18-gage
thermostat
wire).
See
that
me¬
tering
hole,
sealing
surface
around
piston
cones
and
fluted
portion
of
piston
are
not
damaged.
7.
Use
the
chart
on
the
unit
access
panel
to
determine
proper
arrangement
and
size
of
piston.
See
Table
13
for
piston
sizes.
8.
Clean
piston
refrigerant-metering
orifice.
9.
Replace
retainer
0-ring
(part
no.
99CC501052).
Liquid
Line
Strainer
The
liquid
line
strainer
(t<
protect
metering
device)
is
made
of
wire
mesh
and
locate*
in
the
liquid
line
on
inlet
side.
Strainer
is
pressed
into
th
line.
Remove
strainer
by
threading
a
no.
10
sheet-metal
scre>
into
strainer
and
pulling
the
screw
with
pliers.
FLARE
NLfT
STRAINER
RETAINER
COOLING
FLARE
NUT
Fig.
16
~
Metering
Device
Components
25

Related product manuals