TABLE NAME DISPLAY NAME VALUES UNITS POINT NAME WRITE STATUS
SCHEDOVR
CCN Schedule Number 0 = Always Occupied,
1 --- 6 4 = L o c a l S c h e d u l e ,
65--- 99 = Global Schedule
SCHEDNUM 0
Accept Global Holidays? Yes/No HOLIDAYT No
Global Schedule Broadcst Ye s/No CCN_GSBC No
Timed Override Duration 0to4 hours OTL_CFG 4
Timed Override Remaining 0 to 240 min OVR_EXT Forcible
Remote Occupancy Channel 0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB Y3
RMOCCHAN 0=None
Allow Global Overrides Yes/No GLBLOVER Yes
Allow SPT Ovrd Cancel Yes/No CLROVCFG No
BAS_CFG
BAS Protocol Select 0=NONE,
1=CCN,
2=BACNET
BMS_CFG 2=BACNET
Network Input Timeout 0 to 600 min NETINTO 30
CCN Bus Number 0 t o 239 CCNBUS 0
CCN Element Number 1 to 239 CCNADD 1
CCN Baud Rate 0=9600,
1=19200,
2=38400
BAUDENUM 2
BACnet ID Number 0 to 4194302 BAC_ID 1610101
BACnet Device Macaddress 1 to 127 BAC_MAC 1
BACnet BMS baud rate 0=9600,
1=19200,
2=38400,
3=57600,
4=76800,
5=115200
BAC_BAUD 4=76800
BACnet ID Auto ID Yes/No BAC_AUID Yes
ALC Auto Id Scheme Yes/No AUID Yes
BACNET
BACnet ID Number 0 to 4194302 BAC_ID 1610101
BACnet Device Macaddress 1 to 127 BAC_MAC 1
BACnet BMS baud rate 0=9600,
1=19200,
2=38400,
3=57600,
4=76800,
5=115200
BAC_BAUD 4=76800
BACnet ID Auto ID Yes/No BAC_AUID Yes
ALC Auto Id Scheme Yes/No AUID Yes
BACnet device for IAQ 0 to 4194303 DEVIAQ 1610100
Object instance for IAQ 0 to 9999 OBJIAQ 1009
Change of value for IAQ 0to60 COVIAQ 0
BACnet device for OAQ 0 to 4194303 DEVOAQ 1610100
Object instance for OAQ 0 to 9999 OBJOAQ 285
Change of value for OAQ 0to60 COVOAQ 0
BACnet device for OARH 0 t o 4194303 DEVOARH 1610100
Object instance for OARH 0 t o 9999 OBJOARH 1022
Change of value for OARH 0to60 COVOARH 0
BACnet device for OAT 0 to 4194303 DEVOAT 1610100
Object instance for OAT 0 to 9999 OBJOAT 1003
Change of value for OAT 0to60 COVOAT 0
BACnet device for RARH 0 to 4194303 DEVRARH 1610100
Object instance for RARH 0 to 9999 OBJRARH 30
Change of value for RARH 0to60 COVRARH 0
BACnet device for RAT 0 to 4194303 DEVRAT 1610100
Object instance for RAT 0 to 9999 OBJRAT 1010
Change of value for RAT 0to60 COVRAT 0
BACnet device for SPT 0 t o 4194303 DEVSPT 1610100
Object instance for SPT 0 to 9999 OBJSPT 2007
Change of value for SPT 0to60 COVSPT 0
Allow Local Sched Edit Yes/No LCL_EDIT