APPENDIX E: BACnet Points List
Analog Value (AV) Points (cont)
POINT DESCRIPTION POINT ACCESS UNITS
BACnet OBJECT
NAME
BACnet ID VALUE RANGE
CCN POINT
EQUIVALENT
Compressor A1 Starts READ ONLY st_a1 AV:134 0 TO 999999 ST_A1
Compressor A1 strikes READ ONLY a1strike AV:192 0TO3 A1STRIKE
Compressor A1 Timeguard READ ONLY sec timgd_a1 AV:162 0 TO 600 TIMGD_A1
Compressor Min Off Time R/W sec c_minoff AV:202 120 TO 600 C_MINOFF
Compressor Min On Time R/W sec c_minon AV:203 180 TO 600 C_MINON
COOL DMD Offset level 1 R/W °F cdlm_level1 AV:400 0TO40 CLDOLEV1
COOL DMD Offset level 2 R/W °F cdlm_level2 AV:401 0TO40 CLDOLEV2
COOL DMD Offset level 3 R/W °F cdlm_level3 AV:402 0TO40 CLDOLEV3
Cool Mode Select T.guard READ ONLY sec cl_sel_timeguard AV :40 0 TO 65535 COOLMSTG
Cool Setpoint in Effect READ ONLY °F csp_eff AV:208 55 TO 95 CSP_EFF
Cool Shed 1 demand band R/W coolsh1 AV:6014 0TO55 COOLSH1
Cool Shed 2 demand band R/W coolsh2 AV:6015 0TO55 COOLSH2
Cool Shed 3 demand band R/W coolsh3 AV:6016 0TO55 COOLSH3
Cooling Demand Trend READ ONLY cldtrend AV:205 --- 99 TO 99 CLDTREND
Cooling Fan ---Off Delay R/W sec cool_fod AV:207 0 TO 600 COOL_FOD
Damper Actual Position R/W % oa_dmpr_pos AV:2022 0TO1 DAMPPOS
Damper SAT deadband R/W °F t24satdb AV:308 0TO20 T24SATDB
Delay On Low SST Check R/W sec sstckdly AV:300 0 TO 300 SSTCKDLY
Diff. Dry Bulb Deadband R/W °F oa_ra_diff_temp AV:78 1.0f TO 99.0f OATRATDB
Differential Air Quality READ ONLY PPM aq_diff AV:195 --- 5000 TO 5000 AQ_DIFF
Econ Damper Resets Count READ ONLY rs_damp AV:102 0 TO 65535 RS_DAMP
Econ Damper Run Hours READ ONLY hrs hour_damp AV:51 0 TO 999999 HR_DAMP
Econ Max Damper Position R/W % dampmax AV:185 0TO1 DAMPMAX
Econ Min at Max Fanspeed R/W % minp_max AV:318 0TO1 MINP_MAX
Econo Actual Position READ ONLY % dampact AV:211 0TO1 DAMPACT
Econo Commanded Position R/W % dmpr_cmd AV:4 0TO1 DAMPCMD
Economizer Damper Starts READ ONLY st_damp AV:139 0 TO 999999 ST_DAMP
Economizer Position Test R/W % s_damper AV:118 0TO1 S_DAMPER
Economizer Travel Time R/W sec eceonotrv AV:226 5 TO 300 ECONOTRV
Effective Deadband R/W effdb AV:6007 0TO55 EFFDB
Effective Demand Temp READ ONLY °F temp_eff AV:163 --- 40 TO 245 TEMP_EFF
EffectiveZoneSetpoint R/W °F effsp AV:6006 55 TO 90 EFFSP
Enthalpy Cross Deadband R/W BTU_LB oa_ra_diff_enth AV:77 0TO20 OAERAEDB
Equipment Touch RH R/W % EquipmentTouchRH AV:1904 0TO1 ETSPRH
Equipment Touch SPT R/W °F EquipmentTouchSPT AV:1902 --- 40 TO 240 ETSPT
Fan Supply Air Temp READ ONLY °F idf_sa_temp AV:10 --- 40 TO 245 FST
FBDH Low Set Point R/W °Fdelta fbdlosp AV:438 --- 2 0 T O 0 FBDLO_SP
FBDH Max Fan Speed R/W RPM fdrpmmax AV:8057 0 TO 5000 FDRPMMAX
FBDH Min Fan Speed R/W RPM fdrpmmin AV:8056 0 TO 5000 FDRPMMIN
FBDH SAT Min value R/W °F fbdh_sat AV:436 35 TO 80 FBDH_SAT
FBDH SAT Set Point READ ONLY °F fbdsatsp AV:441 0 TO 240 FBDSATSP
FBDH SST Min value R/W °F fbdh_sst AV:437 10 TO 60 FBDH_ S ST
Filter hour remaining READ ONLY hrs filter_rntm AV:2015 0 TO 9999 FILTLEFT
Free Cooling Max OAT R/W °F max_free_cl_temp AV:67 0TO90 MAXFREET
Free Co oling Min Temp R/W °F min_free_cl_temp AV:71 --- 30 TO 70 MINFREET
Free Cooling Reset Count READ ONLY rs_freec AV:104 0 TO 65535 RS_FREEC
Free Cooling Run Hours READ ONLY hrs hour_free_cl AV :53 0 TO 999999 HR_FREEC
Free Cooling Starts READ ONLY st_freec AV:141 0 TO 999999 ST_FREEC
Full Load Resets Count READ ONLY rs_fload AV:103 0 TO 65535 RS_FLOAD
Heat Demand Level Up R/W °F hadmd_lup AV:239 --- 2 T O 2 HDMD_LUP
Heat DMD Offset level 1 R/W °F hdlm_level1 AV:403 0TO40 HTDOLEV1
Heat DMD Offset level 2 R/W °F hdlm_level2 AV:404 0TO40 HTDOLEV2
Heat DMD Offset level 3 R/W °F hdlm_level3 AV:405 0TO40 HTDOLEV3
Heat Minimum Off Time R/W sec h_minoff AV:235 60 TO 600 H_MINOFF
Heat Minimum On Time R/W sec h_minon AV:236 60 TO 600 H_MINON
Heat Mode Select T.guard READ ONLY sec ht_sel_timeguard AV:45 0 TO 65535 HEATMSTG
Heat Setpoint in Effect READ ONLY °F hsp_eff AV:243 40 TO 80 HSP_EFF
Heat Shed 1 demand band R/W heatsh1 AV:6011 0TO55 HEATSH1
Heat Shed 2 demand band R/W heatsh2 AV:6012 0TO55 HEATSH2
Heat Shed 3 demand band R/W heatsh3 AV:6013 0TO55 HEATSH3
Heat Space Demand Trend READ ONLY htdtrend AV:244 --- 99 TO 99 HTDTREND
Heat Stage 1 Reset Count READ ONLY rs_htr_1 AV:106 0 TO 65535 RS_HTR_1
Heat Stage 1 Run Hours READ ONLY hrs hour_ht_1 AV:54 0 TO 999999 HR_HTR_1
Heat Stage 1 Starts READ ONLY st_htr_1 AV:142 0 TO 999999 ST_HTR_1