APPENDIX E: BACnet Points List
Analog Value (AV) Points (cont)
POINT DESCRIPTION POINT ACCESS UNITS
BACnet OBJECT
NAME
BACnet ID VALUE RANGE
CCN POINT
EQUIVALENT
Restore Completion Time READ ONLY rstcomtm AV:337 0 TO 65535 RSTCOMTM
Return Air Enthalpy R/W BTU_LB ra_enth AV:95 --- 9.6f TO 334.2f RA_ENTH
Return Air Temp Sensor READ ONLY °F rat_loc AV:291 --- 40 TO 245 RAT_LOC
Return Air Te mpe rature R/W °F ra_temp AV:1010 --- 40 TO 245 RAT
RLV_A Resets Count READ ONLY rs_rlv_a AV:456 0 TO 65535 RS_RLV_A
RLV_A Starts READ ONLY st_rlv_a AV:460 0 TO 999999 ST_RLV_A
SA Tempering Set point R/W °F sup_air_temp_setpt AV:411 --- 20 TO 60 SATEMPSP
Service Test Reset Count READ ONLY rs_stest AV:116 0 TO 65535 RS_STEST
Service Test Run Hours READ ONLY hrs hour_serv_tst AV:63 0 TO 999999 HR_STEST
Service Test Starts READ ONLY st_stest AV:151 0 TO 999999 ST_STEST
Setpoint adjustment R/W °Fdelta setadj AV:6021 0TO1 SETADJ
Single Zone Setpoint R/W °F zonespt AV:6001 55 TO 80 ZON E SPT
Software Build Time READ ONLY fw_bldtm AV:169 0 TO 4294967295 FW_BLDTM
Space Cooling Demand READ ONLY °Fdelta cool_dmd AV:206 --- 100 TO 100 COOL_DMD
Space Demand Time Guard1 R/W sec tdmd_tg1 AV:311 60 TO 600 TDMD_TG1
Space Demand Time Guard2 R/W sec tdmd_tg2 AV:186 0 TO 600 TDMD_TG2
Space Demand Time Guard3 R/W min tdmd_tg3 AV:187 5 TO 120 TDMD_TG3
Space RH R/W % space_rh AV:1011 0TO1 SPRH
Space RH Deadband R/W % sprh_db AV:368 0TO1 SPRH_DB
Space Temperature R/W °F space_t AV:296 --- 40 TO 245 SP ACE_T
Space Tempe rature Offset R/W °Fdelta stpt_adj AV:1006 --- 10 TO 10 SPTO
Space Temperature Sensor READ ONLY °F spt_loc AV:297 --- 40 TO 245 SPT_LOC
SPRH Assigned Channel R/W sprhchan AV:372 0TO3 SPRHCHAN
SPRH Sensor V alue @ 20mA R/W % sprh_20ma AV:373 0.6 TO 1 SPRH20MA
SPRH Sensor V alue at 4mA R/W % sprh_4ma AV:375 0TO0.5 SPRH_4MA
SPT Offset Range (+/--- ) R/W °F spto_rng AV:298 0TO5 SPTO_RNG
SPT Offset Total diff READ ONLY °Fdelta sptodiff AV:6020 0TO20 SPTODIFF
Std Barometric Pressure R/W IN_HG_OF_KPAG std_barp AV:303 10 TO 35 STD_BARP
Supply Air Temp Trend READ ONLY sattrend AV:342 --- 285 TO 285 SATTREND
Supply Air Temperature READ ONLY °F sa_temp AV:1008 --- 40 TO 245 SAT
System Demand READ ONLY sys_demand AV:37 0 TO 255 SYS_DMD
System Demand Alert R/W sys_dmd_alert AV:227 0 TO 65535 SYSDMDAT
System Touch AI for SPRH R/W aistsprh AV:8027 0 TO 9999 AISTSPRH
System Touch AI for SPT R/W aistspt AV:8026 0 TO 9999 AISTSPT
System Touch Device Inst R/W devst AV:8024 0 TO 4194303 DEVST
System Touch Poll Rate R/W pollst AV:8025 10 TO 60 POLLST
System Touch RH Value R/W % strh_net AV:8022 0TO1 STRH_NET
System Touch Temp Value R/W °F stst_net AV:8023 --- 40 TO 245 STST_NET
T24 Heat/Cool End Delay R/W min t24chdly AV:305 0TO60 T24CHDLY
T24 Min Diff in RAT--- OAT R/W °F t24ratdf AV:307 5TO20 T24RATDF
T24 Test Maximum Pos R/W % t24tstmx AV:310 0.0f TO 1.0f T24TSTMX
T24 Test Minimum Pos R/W % t24tstmn AV:309 0.0f TO 1.0f T24TSTMN
T24Econ Min Move for SAT R/W % t24ecsts AV:306 0.1 TO 0.2 T24ECSTS
Timed Override Duration R/W hrs otl_cfg AV:179 0TO4 OTL_CFG
Timed Override Hours R/W min ovr_ext AV:180 0 TO 240 OVR_EXT
TLO cancel R/W sec tlocan AV:6029 0TO10 TLOCAN
TLO limit R/W sec tlolim AV:6027 0 TO 14400 TLOLIM
TL O Time Remaining READ ONLY sec tlorem AV:6028 0 TO 14400 TLOREM
UFC PreOcc Time R/W min ufctime AV:105 1 TO 999 UFCTIME
Unit Full Load Run Hours READ ONLY hrs hour_full_ld AV:52 0 TO 999999 HR_FLOAD
Unit Full Load Starts READ ONLY st_fload AV:140 0 TO 999999 ST_FLOAD
Unit Startup Delay R/W sec startdly AV:153 10 TO 600 STARTDLY
Unocc Free Cool Low Temp R/W °F oatlufc AV:287 --- 30.0f TO 70.0f OATLUFC
Unoccupied Cool Setpoint R/W °F ucsp AV:8 65 TO 95 UCSP
Unoccupied Heat Setpoint R/W °F uhsp AV:178 40 TO 80 UHSP
Unoccupied Setpoint Gap R/W udb AV:6004 0TO55 UDB
Unoccupied SPRH Setpoint READ ONLY % sprh_usp AV:461 0.10 TO 1 SPRH_USP
UnoccupiedZone Setpoint R/W °F usp AV:6005 40 TO 95 USP
User Min Pos Pnt 1 Valid READ ONLY mp_upt1 AV:332 0TO1 MP_UPT1
User Min Pos Pnt 2 Valid READ ONLY mp_upt2 AV:333 0TO1 MP_UPT2
User Min Pos Pnt 3 Valid READ ONLY mp_upt3 AV:214 0TO1 MP_UPT3
User Password R/W password AV:181 0 TO 9999 PASSWORD
Value of Prime variable READ ONLY prime_v AV:39 --- 40 TO 245 PRIME_V
V ent IDF Resets Count READ ONLY rs_ventf AV:117 0 TO 65535 RS_VENTF