APPENDIX E: BACnet Points List
Binary Value (BV) Points
POINT DESCRIPTION POINT ACCESS UNITS
BACnet OBJECT
NAME
BACnet ID VALUE RANGE
CCN POINT
EQUIVALENT
2--- Pos Damper/ERV relay R/W erv_2pos BV:6002 0TO1 ERV_2POS
2Position/ERV Relay Test R/W s_erv2p BV:457 0TO1 S_ERV2P
A051 Cmp off expected ON R/W a_caoff BV:181 0TO1
Act Mech Disconnect Alrt R/W a_dnmemd BV:218 0TO1 1
Air Quality CO2 Alerts R/W co2s_al BV:307 0TO1 CO2S_AL
Alarm Output Relay State R/W equip_alarm BV:7048 0TO1 ALMOUT
Alarm Output Relay Test R/W s_alarm BV:70 0TO1 S_ALARM
Alarm Reporting Enable R/W ALARMEN BV:27 0TO1 ALARMEN
ALC Auto Id Scheme R/W auid BV:106 0TO1 AUID
All Heat Stages Lockout R/W allhtloc BV:122 0TO1 ALLHTLOC
AUTO INDEPENDENT TEST R/W autoindp BV:163 0TO1 AUTOINDP
BACnet BMS Schedule READ ONLY bms_sced BV:108 0TO1 BMS_SCED
BACnet ID Auto ID R/W bac_auid BV:107 0TO1 BAC_AUID
BACnetCal Object Status READ ONLY calobjst BV:110 0TO1 CALOBJST
B a d D D P o i n t --- O u t O f R a n g e R/W f_bad_dd BV:243 0TO1
CA1 DDF Fault R/W f_ca1ddf BV:178 0TO1
CA1 FTP alert R/W a_ca1ftp BV:182 0TO1
CA1 Rev Rotation alert R/W a_ ca1rr BV:179 0TO1
CCH Relay 1 State READ ONLY cch_relay BV:3 0TO1 CCHR1
Cir A DDF Fault R/W f_caddf BV:168 0TO1
Cir A HDP alert R/W a_cahdp BV:172 0TO1
Cir A HPS alert R/W a_ cahps BV:171 0TO1
Cir A LDP Alert R/W a_caldp BV:236 0TO1
Cir A LSP Alert R/W a_calsp BV:170 0TO1
Cir A Press Ratio Alert R/W a_capr BV:169 0TO1
Cir A SSP out Rng Alert R/W a_badspa BV:189 0TO1
Cir.A High Pressure Sw READ ONLY circa_hps BV:4 0TO1 CIRA_HPS
Circ A SDP Open Alert R/W a_opndpa BV:191 0TO1
Circ A SDP range alert R/W a_baddpa BV:183 0TO1
Circ A SDP Short Alert R/W a_shtdpa BV:202 0TO1
Circ A SSP Open Alert R/W a_opnspa BV:200 0TO1
Circuit A CMP A1 Loader READ ONLY cmpalena BV:9 0TO1 COMP_ALD
Circuit A Compressor 1 READ ONLY cmpa1ena BV:5 0TO1 COMP_A1
Circuit A Locked Out READ ONLY ciralock BV:128 0TO1 CIRAL OCK
Circuit A SSP Shrt Alert R/W a_shtspa BV:211 0TO1
C k t --- A l o w c h a r g e f a u l t R/W f_caloch BV:167 0TO1
Clear Alarm History R/W alarm_hist_clear BV:32 0TO1 ALHISCLR
CmpBumpLoaderTest R/W s_bmpald BV:64 0TO1 S_BMPALD
COFS Switch State R/W condensate_switch BV:7028 0TO1 COFS
Compressor A1 Available READ ONLY ca1_aval BV:123 0TO1 CA1_AVAL
Compressor A1 Locked Out READ ONLY ca1_lock BV:124 0TO1 CA1_LOCK
Compressor Alerts R/W comp_alarm BV:312 0TO1 COMP_AL
Compressor Bump A1 Test R/W s_bmpa1 BV:71 0TO1 S_BMPA1
CompressorStuck on Fault R/W f_cstuck BV:241 0TO1
Condensate Ovrflow fault R/W f_cofs BV:273 0TO1
CoolDemandLimiting R/W cooldmdLimit BV:435 0TO1 CDMLMOFF
Cooling Liq Valv Test R/W s_clv_a BV:456 0TO1 S_CLV_A
Cooling Liq Valve CirA R/W clv_a BV:7052 0TO1 CLV_A
Cooling W/Comp.A1 Test R/W s_coola1 BV:74 0TO1 S_COOLA1
Cooling W/Comp.ALD Test R/W s_cola1d BV:79 0TO1 S_COLALD
Crankcase Heater 1 test R/W s_cchr1 BV:73 0TO1 S_CCHR1
Currently Occupied R/W occ_status BV:2008 0TO1 OCCUPIED
Damper fdbk out of range R/W a_badec1 BV:184 0TO1
Damper fdbk Short Alert R/W a_shtec1 BV:203 0TO1
Damper Not Mod Alert R/W a_dnm BV:215 0TO1
Damper Stuck Closed Alrt R/W a_ dnm_sc BV:216 0TO1
Damper Stuck Open Alert R/W a_dnm_so BV:217 0TO1
Diff. Dry Bulb Control R/W dif_db_ena BV:41 0TO1 DIFFBULB
Diff. Enthalpy Control R/W dif_enth_ena BV:42 0TO1 DIFFENTH
dirty filter alert R/W a_dfilt BV:214 0TO1
Dirty Filter Alerts R/W filter_alarm BV:7017 0TO1 FILT_AL
Dmpr fdbk Open Cir Alert R/W a_opnec1 BV:192 0TO1
Dry Bulb Lockout R/W db_lock_out BV:40 0TO1 DBLOCK
DST allowed? R/W dst_cfg BV:93 0TO1 DST_CFG