APPENDIX E: BACnet Points List
Binary Value (BV) Points (cont)
POINT DESCRIPTION POINT ACCESS UNITS
BACnet OBJECT
NAME
BACnet ID VALUE RANGE
CCN POINT
EQUIVALENT
MBB RNET Voltage Alert R/W a _ mbb12d BV:246 0TO1
MBB zero crossing alert R/W a_mbb0x BV:245 0TO1
Mechanical Cool active? READ ONLY mechcool BV:301 0TO1 MECHCOOL
OACFM Alarm Relay R/W oacfm_rel_alarm BV:371 0TO1 OACFM_AL
OACFM Open Circuit Alert R/W a_ opnoac BV:276 0TO1
OACFM ShortCircuit Alert R/W a_shtoac BV:277 0TO1
OAQ Open Circuit Alert R/W a_opnoaq BV:195 0TO1
OAQ Short Circuit Alert R/W a_shtoaq BV:206 0TO1
OARH Open Circuit Alert R/W a_opnorh BV:197 0TO1
OARH Sensor Error R/W oarh_err BV:60 0TO1 OARH_ERR
OARH Short Circuit Alert R/W a_shtorh BV:208 0TO1
OAT Open Circuit Alert R/W a_opnoat BV:196 0TO1
OAT out of Range Alert R/W a_badoat BV:186 0TO1
OAT Sensor Error R/W oat_error BV:314 0TO1 OAT_ERR
OAT Short Circuit Alert R/W a_shtoat BV:207 0TO1
OAT Thermistor Alerts R/W oat_rel_alarm BV:61 0TO1 OATRL_AL
ODF Speed Relay Test R/W s_ofrspd BV:6001 0TO1 S_OFRSPD
Ok to fan based dehum READ ONLY oktofbd BV:420 0TO1 OKTOFBD
Ok to Dehumidify? READ ONLY oktodhum BV:422 0TO1 OKTODHUM
Ok to Preoccupancy Purge READ ONLY okpreocc BV:35 0TO1 OKPREOCC
OK to Run Heat READ ONLY oktoheat BV:36 0TO1 OKTOHEAT
OK to SupplyAirTempering READ ONLY oktotemp BV:415 0TO1 OKTOTEMP
Ok to Unocc Free Cool? READ ONLY oktoufc BV:37 0TO1 OKTOUFC
Ok to use compressors? READ ONLY okmechcl BV:302 0TO1 OKMECHCL
OKtoUseFreeCooling? READ ONLY ok_free_cl BV:65 0TO1 OKFREECL
Ok to use humidimizer READ ONLY oktohumz BV:421 0TO1 OKTOHUMZ
Outdoor Fan Speed Relay R/W ofr BV:6000 0TO1 OFR
Percent Enable/Disable R/W perc_bac BV:303 0TO1 PERC_BAC
Phase Monitor Fault READ ONLY f_phmon BV:279 0TO1
Power Exhaust 1 Relay R/W pe1 BV:15 0TO1 PE1
Power Exhaust 1 T est R/W s_pe_1 BV:82 0TO1 S_PE_1
Power Exhaust 2 Relay R/W pe2 BV:66 0TO1 PE2
Power Exhaust 2 T est R/W s_pe_2 BV:83 0TO1 S_PE_2
RARH Open Circuit Alert R/W a_opnrrh BV:199 0TO1
RARH Sensor Error R/W rarh_err BV:67 0TO1 RARH _ERR
RARH Short Circuit Alert R/W a_shtrrh BV:210 0TO1
RAT Open Circuit Alert R/W a_opnrat BV:198 0TO1
RAT out of Ra nge Alert R/W a_badrat BV:187 0TO1
RAT out of Ra nge Alert R/W a_badsat BV:188 0TO1
RAT Sensor Error R/W rat_err BV:68 0TO1 RAT_ERR
RAT Short Circuit Alert R/W a_shtrat BV:209 0TO1
Refrig Circuit Alerts R/W circuit_alarm BV:313 0TO1 CKT_AL
Reheat Dischg Valve CirA R/W rdv_a BV:7012 0TO1 RDV_A
Reheat Liq Valv Rly Test R/W s_rlv_a BV:455 0TO1 S_RLV_A
Reheat Liquid Valve CirA R/W rlv_a BV:7051 0TO1 RLV_A
Remote Occupancy Switch R/W remocc BV:29 0TO1 REMOCC
Remote shutdown fault R/W f_remoff BV:272 0TO1
Remote Shutdown Switch R/W rem_shut BV:9001 0TO1 REMSHUT
Reset All Current Alarms R/W alarm_reset BV:33 0TO1 ALRESET
Reset Filter Timer R/W reset_filter_timer BV:109 0TO1 RESETFLT
RH sensor failure Alert R/W rhs_al BV:308 0TO1 RHS_AL
Rht Dischg Valve Rly Tst R/W s_rdv_a BV:282 0TO1 S_RDV_A
Rollout without Heating R/W f_ronoht BV:235 0TO1
RUN AUTO COOLING TEST R/W autocool BV:160 0TO1 AUTOCOOL
RUN AUTO HEATING TEST R/W autoheat BV:161 0TO1 AUTOHEAT
RUN AUTO SYSTEM TEST R/W autosys BV:162 0TO1 AUTOSYS
Run away heat fault R/W f_hstuck BV:266 0TO1 0TO1
SAT Sensor Error R/W sat_err BV:84 0TO1 SAT_ERR
SAT/RAT Sensor Alerts R/W sa_ra_alarm BV:311 0TO1 SATRATAL
SDP A Sensor Error R/W sdpa_err BV:63 0TO1 SDPA_ERR
Shut Down on IDF Failure R/W sfan_fail_alarm BV:7008 0TO1 FATALFAN
Shutdown A1 First R/W sdwn_a1 BV:449 0TO1 SDWN_A1
Shutdown Loader First R/W sdwn_ald BV:451 0TO1 SDWN_ALD
Smoke Purge Input R/W purge BV:80 0TO1 PURGE