64
APPENDIX A: SystemVut Controller Display
Settings Main Menu Layout (cont)
DISPLAY TEXT EXPANDED DISPLAY TEXT VALUES UNITS DEFAULT POINT
CLOCK (cont) Clock Adjustment Menu
DST STOP MONTH DST Stop Month 1=JANUARY,
2=FEBRUARY,
3=MARCH,
4=APRIL,
5=MAY,
6=JUNE,
7=JULY,
8=AUGUST,
9=SEPTEMBER,
10=OCTOBER,
11=NOVEMBER,
12=DECEMBER
11 STOPM
DST STOP WEEK DST Stop Week 1to5 1 STOPW
DST ST OP DAY DST Stop Day 1=MONDAY,
2=TUESDAY,
3=WEDNESDAY,
4=THURSDAY,
5=FRIDAY,
6=SATURDAY,
7=SUNDAY
7 STOPD
DST MINS TO SUB DST Minutes to Subtract 0to90 min 60 MINSUB
START TIME IN DA Y Time in day to start DST 0 t o 600 min 120 DST_TOD
SCHEDULES Schedules Adjustment Menu
SCHEDULE NUMBER CCN Schedule Number 0 = Always Occupied,
1 --- 6 4 = L o c a l S c h e d u l e ,
65--- 99 = Global Schedule
0 = Always Occupied SCHEDNUM
OCCUPANCY SCHEDULE OCCUPANCY SCHEDULE DATA
Holiday adjustment Menu Holiday adjustment Menu
ALLOW G. HOLIDAY? Accept Global Holidays? Yes/No No HOLIDAYT
TIMED OVR LENGTH Timed Override Duration 0to4 hrs 4 OTL_CFG
CAN CANCEL T.OVR Allow SPT Ovrd Cancel Yes/No No CLROVCFG
UNIT CONFIGURATIONS Unit Configurations Menu
GENERAL General Unit Configurations Menu
STARTUP DELAY Unit Startup Delay 10 to 600 sec 30 STARTDLY
UNIT CONTROL TYPE Unit Control Type 0=TSTAT,
1=SPACE SEN,
2=RAT SEN
0=TSTAT CTRLTYPE
THERMOSTA T TYPE Thermostat Hardware Type 0=CONV 2C2H,
1=DIGI 2C2H,
2=CONV 3C2H,
3=DIGI 3C2H
0=CONV 2C2H STA TTYPE
VENT METHOD Ventilation Method 0=NONE,
1=ECON,
2=2POS DMPR,
3=ERV,
4=ECON ERV
0: No FIOP
1: Economizer FIOP
2: Two Position Damper
FIOP
VENTTYPE
2POS/ERV CHANNEL 2--- Pos Damper/ERV Channel 0=NONE,
1=MBB RLY11,
2=MBB RLY06,
0: No FIOP
2: FIOP
EV2PCHAN
ADAPTIVE TSTAT Tstat Adaptive Staging Yes/No Yes ADPTSTAT
DIRTY FILTER TIME Change Filter Timer 0 to 9999 hrs 600 FILTLIFE
TEST MODE TIMEOUT Test inactivity time out 0=Disabled,
1=30 minutes,
2=1 hour,
3=2 hours,
4=4 hours,
5=8 hours,
6=12 hours
4 TEST_ITO
CCH MAX TEMP CCH Max Temperature 40 to 90 °F 65 CCHMAXT
STD BARO PRESSURE Std B arometric Pressure 13 to 35 Hg 29.92 STD_BARP
LINK STAGEUP TIME Linkage Stage inc. time 60 to 600 sec 180 LST AGINC
UNIT’S MAX SAT Unit’s Maximum SAT 130 to 210 °F 200 UMAX_SAT
AUTO SAT FAULTS? Auto Clr SAT Limit Fault Yes/No No SATLACLR
ADAPTIVE TCS? Adaptive Temp Comp Start Enable/Disable Enable TCS_CFG
USER TCS BIASTIME User TCS Start Bias Time 0 to 180 min 0 TCSUBIAS
SWITCH INPUTS CONFIGS DI Config Menu
FIRE SHUTDOWN SW Fire Shutdown Switch 0=NORM OPEN,
1=NORM CLSD,
2=NO SWITCH
2: no FIOP
0: FIOP
FIRE_CFG
HUMSTAT CHANNEL Humidistat Status Chan. 0=None,
1=MBB DI12,
2=MBB DI13.
3=MBB DI14,
4=MBB DI02,
5=MBB Y3
0 : N o H u m i d i --- M i Z e r
FIOP
5 : H u m i d i --- M i Z e r F I O P
HUMDCHAN
HUMSTAT SW TYPE Humidistat Switch Type 0=NORM OPEN,
1=NORM CLSD,
0=NORM OPEN HUMD_CFG