70
APPENDIX A: SystemVut Controller Display
Settings Main Menu Layout (cont)
DISPLAY TEXT EXPANDED DISPLAY TEXT VALUES UNITS DEFAULT POINT
ALARM RELAY Alarm Relay Configurations Menu
ALM RELAY CHANNEL ALM Relay Assigned Chan 0=NONE,
1=MBB RLY11,
2=MBB RLY06
1=MBB RLY11 ALM_CHAN
THERMOSTAT ALERTS Thermostat Alerts Yes/No Yes TSTAT_AL
HARDWARE ALERTS Hardware Failures Alerts Yes/No Yes HW_AL
SAT/RAT ALERTS SAT/RAT Sensor Alerts Ye s/No Yes SATRA TAL
OAT SENSOR ALERTS OAT Thermistor Alerts Ye s/No Yes OATRL_AL
SPACE SENS ALERTS Space Sensors Alerts Yes/No Yes SP ACE_AL
TRANSDUCER ALERTS Transducer Sensor Alerts Yes/No Yes TRANS_AL
RH SENSOR ALERTS RH sensor failure Alert Yes/No Yes RHS_AL
CO2 SENS OR ALERTS Air Quality CO2 Alerts Yes/No Yes CO2S_AL
OACFM SENS ALERTS OACFM Alarm Relay Yes/No No OACFM_AL
ECONOMIZER ALERTS Economizer Alerts Yes/No Yes ECON_AL
AIRFILTERALERTS Dirty Filter Alerts Yes/No Yes FILT_AL
GEN STATUS ALERTS General Status Alerts Yes/No Yes GENS_AL
REFRIG CIR ALERTS Refrig Circuit Alerts Yes/No Yes CKT_AL
COMPRESSOR ALERTS Compressor Alerts Ye s/No Yes COMP_AL
HEATING ALERTS Heating Failure Alerts Yes/No Yes HEAT_AL
INDOOR FAN ALERTS Indoor Fan Alerts Ye s/No Yes FAN_AL
ON ACTIVE FAULTS Relay On Active Faults Yes/No Yes FAULT_AL
SERVICE CONFIG MENU Service Configuration Menu
CMP FRAMEWORK Compressor Framework 0=1CIR 2CMP,
1=1CMP+LDR,
2=1CMP
1: All except below
2: 48/50FC 04--- 06
SYSVTYPE
SHUTDWN A1 FIRST Comp A1 Shutdown First Ye s/No No SDWN_A1
SHUTDWN ALD FIRST Comp Loader Shutdown 1st Ye s/No Yes: All except below
No: 48/50FC 04--- 06
SDWN_ALD
IDF CURVE LO RPM IDF Curve Low End RPM 0 t o 3000 RPM 189: Size 04 Standard Static
Fan
219: Size 04 Medium Static
Fan
249: Size 04 High Static Fan
190: Size 05 Standard Static
Fan
217: Size 05 Medium Static
Fan
246: Size 05 High Static Fan
230v 1 ph
266: Size 05 High Static Fan
230v 3ph, 460v, 575v
215: Size 06 Standard Static
Fan
239: Size 06 Medium Static
Fan
266: Size 06 High Static Fan
230v 1 ph
284: Size 06 High Static Fan
230v 3ph, 460v, 575v
230: Size 07 Standard Static
Fan
253: Size 07 Medium Static
Fan
284: Size 07 High Static Fan
IFMLORPM
IDF CURVE HI RPM IDF Curve High End RPM 0 t o 3000 RPM 1890: Size 04 Standard Stat ic
Fan
2190: Size 04 Medium Static
Fan
2490: Size 04 High Static Fan
1900: Size 05 Standard Static
Fan
2170: Size 05 Medium Static
Fan
2460: Size 05 High Static Fan
230v 1 ph
2660: Size 05 High Static Fan
230v 3ph, 460v, 575v
2150: Size 06 Standard Static
Fan
2390: Size 06 Medium Static
Fan
2660: Size 06 High Static Fan
230v 1 ph
2836: Size 06 High Static Fan
230v 3ph, 460v, 575v
2300: Size 07 Standard Static
Fan
2530: Size 07 Medium Static
Fan
2836: Size 07 High Static Fan
IFMHIRPM