APPENDIX A: SystemVut Controller Display
Settings Main Menu Layout (cont)
DISPLAY TEXT EXPANDED DISPLAY TEXT VA L UES UNITS DEFAULT POINT
BACNET (cont) BACnet network configuration menu
DEVICE RAT BACnet device for RAT 0 to 4194303 1610100 DEVRAT
OBJECT ID RAT Object instance for RAT 0 to 9999 1010 OBJRAT
COV RAT Change of value for RAT 0to60 0 COVRA T
DEVICE SPT BACnet device for SPT 0 to 4194303 1610100 DEVSPT
OBJECT ID SPT Object instance for SPT 0 to 9999 2007 OBJSPT
COV SPT Change of value for SPT 0to60 0 COVSPT
LOCAL_SHEDL_EDIT Allow Local Sched Edit Yes/No enum No LCL_EDIT
SYSTEM TOUCH System Touch Menu
DEVICE INSTAN CE System Touch Device Inst 0 to 4194303 160099 DEVST
POLLING RATE System Touch Poll Rate 10 to 60 10 POLLST
SPACE TEMP AI System Touch AI for SPT 0 to 9999 1 AISTSPT
SPACE RH AI System Touch AI for SPRH 0 to 9999 4 AISTSPRH
ZS SENSOR CFG ZS Sensor Configuration
ZS1 ADDRESS Zone Sensor 1 Address 0 to 255 255 ZSADDR1
ZS2 ADDRESS Zone Sensor 2 Address 0 to 255 255 ZSADDR2
ZS3 ADDRESS Zone sensor 3 address 0 to 255 255 ZSADDR3
ZS4 ADDRESS Zone sensor 4 address 0 to 255 255 ZSADDR4
ZS5 ADDRESS Zone sensor 5 address 0 to 255 255 ZSADDR5
ZS POLL RAT E Zone sensor poll rate 1 to 100 sec 5 ZSPOLLRT
ZS UNIT Zone sensor unit 0=degrees F 0=degrees F ZSUNIT
ZSFRCUNOCENBL ZS Force Unoccup enable Yes/No No ZSFUNEN
ZSFRCUNOCDELAY ZS Force unocc wt delay Yes/No No ZSFUNWT
ZS TLO CONT ENBL ZS TLO Cont Enable Yes/No No ZSTLOEN
TLO SET DURING OC ZS TLO set during occ Yes/No No ZSTL SOC
ZS UI MODE Zone sensor UI Mode 1=Dual Offsets 1=Dual Offsets ZS UIM
NETWORK CHKLIST NETWORK SETUP CHECKLIST 0=Undone,
1=Perfom,
2=Done
0=Undone CHK_NET
DISPLAY SETTINGS User Display Configurations Menu
METRIC DISPLAY Metric Display Yes/No No DISPUNIT
LANGUAGE Display Language Select 0=English,
1=Spanish,
2=French,
3=Portuguese
0=English LANGUAGE
CONTRAST ADJUST LCD Contrast Adjustment 1to10 5 LCD_CONT
PASSWORD ENABLE? User Password Protection Enable/Disable Enable PAS S_EBL
VIEW USER PASSWORD View User Password Menu
CHANGE USER PASSWORD Change User Password Menu
QUICK SETUP CONFIG QUICK SETUP CONFIG MENU
TIME Clock Hour and Minute xx:xx TIME
DATE Current Date MM/DD/YYYY DATE
STARTUP DELAY Unit Startup Delay 10 to 600 sec 30 STARTDLY
UNIT CONTROL TYPE Unit Control Type 0=TSTAT,
1=SPACE SEN,
2=RAT SEN
0=TSTAT CT RLTYPE
THERMOSTA T TYPE Thermostat H ardware Type 0=CONV 2C2H,
1=DIGI 2C2H,
2=CONV 3C2H,
3=DIGI 3C2H
0=CONV 2C2 STATTYPE
DIRTY FILTER TIME Change Filter Timer 0 to 9999 hrs 600 FILTLIFE
HEATING STAGE QTY Number of Heating Stages 0to2 2: all except below
0: 50 Series withou t FIOP heaters
1: 48 Series si n gle phas e power ,
Low Nox Gas Heat,
48FC 04---07 Low Heat,
48FC 05---07 Med Heat,
50GC 04---06 Low Heat,
50GC 04---05 Med Heat,
50GC 04 High Heat 230v 3ph and 460v ,
50GC 05 High Heat 230v 3ph,
50GC 06 Med Heat 460v and 575v
NUMHSTGS
VENT METHOD Ventilation Method 0=NONE,
1=ECON,
2=2POS DMPR,
3=ERV,
4=ECON ERV
0: No FIOP
1: Economizer FIOP
2: Two Position Damper FIOP
VENTTYPE
FREE COOL MAX OAT Free Cooling Max OAT 0to90 °F 65 MAXFREET
FIRE SHUTDOWN SW Fire Shutdown Switch 0=NORM OPEN,
1=NORM CLSD,
2=NO SWITCH
2: no FIOP
0: FIOP
FIRE_CFG
QUICK SET CHKLIST QUICK SETUP CHECKLIST 0=Undone,
1=Perfom,
2=Done
0=Undone CHK_QUIK