EasyManua.ls Logo

Carrier 50FC Series - APPENDIX A: SystemVut Controller Display; Outputs Main Menu Layout

Carrier 50FC Series
144 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
82
APPENDIX A: SystemVut Controller Display
Outputs Main Menu Layout
DISPLAY TEXT EXPANDED DISPLAY TEXT VALUES UNITS WRITE STATUS POINT
OUTPUTS Outputs Menu
GENERAL OUTPUTS General Outputs Menu
COMMANDED IDF RPM IDF Commanded RPM xxxx RPM FSPD_RPM
ECON CMD POSITION Econo Commanded Position 0 to 100 % Forcible DAMPCMD
CCH RELAY CCH Relay 1 State On/Off CCHR1
PE1 RELAY Power Exhaust 1 Relay On/Off Forcible PE1
PE2 RELAY Power Exhaust 2 Relay On/Off Forcible PE2
ALARM RELAY Alarm Output Relay State On/Off Forcible ALMOUT
2POS/ERV RELAY 2--- Pos Damper/ERV relay On/Off Forcible ERV_2POS
COOLING OUTPUTS Cooling Outputs Menu
COMPRESSOR A1 Circuit A Compressor 1 On/Off COMP_A1
COMP A LOADER Circuit A CMP A1 Loader On/Off COMP_ALD
ODF SPEED RELAY Outdoor Fan Speed Relay On/Off OFR
RH DISCH VALVE Reheat Dischg Valve CirA On/Off RDV_A
RH LIQUID VALVE Reheat Liquid Valve CirA On/Off RLV_A
COOL LIQUID VALVE Cooling Liq Valve CirA On/Off CLV_A
HEATING OUTPUTS Heating Outputs Menu
HEAT 1 RELAY Heat Stage 1 Relay On/Off HEAT_1
HEAT 2 RELAY Heat Stage 2 Relay On/Off HEAT_2
USB Main Menu Layout
DISPLAY TEXT EXPANDED DISPLAY TEXT VALUES UNITS WRITE STATUS POINT
USB USB Menu
DATA ACQUISITION Data Acquisition Menu
TREND STATUS US B TREND STATUS 0=IDLE,
1=TRENDING,
2=NO POINTS,
3=USB FULL
TRNDSTAT
TREND DURATION USB TREND DURATION 0=1 MINUTE,
1=5 MINUTES,
2=15 MINUTES,
3=30 MINUTES,
4=1 HOUR,
5=3 HOURS,
6=8 HOURS,
7=12 HOURS,
8=1 DAYS,
9=1.5 DAYS,
10=2 DAYS,
11=3 DAYS,
12=5 DAYS,
13=1 WEEK,
14=2 WEEK,
15=4 WEEK,
16=USB FULL
Command TRNDDUR
TREND RATE USB TREND RATE 1 to 300 Command TRNDRATE
TREND POINTS FROM USB TREND POINTS FROM 0=FILE,
1=LIST
Command TRNDPNTS
TREND FROM USB FILE? TREND FROM USB FILE MENU
TREND FROM PRELIST? TREND FROM PRELIST MENU
EQUIP PERFORMANCE TREND EQUIP PERFORMANCE On/Off Command TRNDEQPR
GEN. INPUT/OUTPUT TREND GEN INPUTS/OUTPUTS On/Off Command TRNDIO
COOL PERFORMANCE TREND COOL PERFORMANCE On/Off Command TRNDCLPR
HEAT PERFORMANCE TREND HEAT PERFORMANCE On/Off Command TRNDHTPR
COOL DIAGNOSTIC TREND COOLING DIAGNOSTIC On/Off Command TRNDCLDG
IDF DIAGNOSTIC TREND IDF DIAGNOSTIC On/Off Command TRNDIDF
VENT DIAGNOSTIC TREND VENTILATION On/Off Command TRNDVENT
TREND GO? Start USB Trending Yes/No Command TREND_EN
SAVE CONFIGS TO FILE Save Configuration to file
SAVE CONFIGS Make Config Backup File Start/Stop Command DDBCKUP
SAVE CONFIG ST ATUS Backup File is ready 0=IDLE,
1=SUCCESS,
2=FAILURE
BACKUP_R
SAVE CONFIGS FROM FILE Save Co nfiguration from file
FIND CONFIG FILE USB Find Restore File Yes/No Command BACKFILE
FILE TRANSFER File Transfer Menu
BACKUP SERVICE FILES BACKUP SERVICE FILES
UPGRADE SOFTWARE Upgrade Software Menu
FIND APPLICATION FILE USB search for app file Yes/No Command APPFILE

Table of Contents

Other manuals for Carrier 50FC Series

Related product manuals