94
APPENDIX C: Navigatort Display
MODE -- OPERATING MODES
ITEM EXPANSION VALUES UNITS WRITE STATUS POINT
OPERATING MODES Operating Modes Menu
MODE Operating Mode see Appendix B MODETEXT
SUBM O p e r a t i n g S u b --- M o d e see Appendix B SUBMTEXT
S.DMD System Demand see Appendix B SYS_DMDT
LINK Linkage Active Yes/No Forcible LNK_ACT
CLTG Cool Mode Select T.guard xxx sec COOLMSTG
HTTG Heat Mode Select T.guard xxx sec HEATMSTG
MODE -- ALARMS
ITEM EXPANSION RANGE
WRITE
STATUS
POINT
ALARMS
CURR Curr Active Alarm Menu
alarm# text string ALARM01C --- ALARM25C
(repeat up to 25 times)
HIST History Menu
alarm# a l a r m # --- m m / d d / y y --- h h. m m --- t e x t s t r i n g ALHIS001 --- ALHIS050
(repeat up to 50 times)
R.CUR Reset All Current Alarms Yes/No Yes ALRESET
R.HIS Alarm Reset History Menu
ARxx mm/dd/yy, hh:mm:ss ALMRES00 --- ALMRES19
(repeat up to 20 times)