99
APPENDIX D: SystemVut Controller CCN Tables
Maintenance Tables
TABLE DISPLAY NAME VALUES UNITS POINT NAME WRITE STATUS
MODES
Operating Mode see Appendix B MODETEXT
System Mode see Appendix B SYSMODE
O p e r a t i n g S u b --- M o d e see Appendix B SUBMTEXT
Running Mode Operation see Appendix B SUB_MODE
Ventilation Status see Appendix B VENTTEXT
Ventilation Status see Appendix B VENTST AT
System Demand see Appendix B SYS_DMDT
System Demand 0to99 SYS_DMD
Currently Occupied Yes/No OCCUPIED Forcible
Linkage Active Yes/No LNK_ACT
Unocc Free Cool Active Yes/No UFC_ACT
Temp Compensate Start On Yes/No TCS_ACT
Current Mode Ended Yes/No MODEDONE
Cool Mode Select T.guard xxx sec COOLMSTG
Heat Mode Select T.guard xxx sec HEATMSTG
Cool Setpoint in Effect xx.x °F CSP_EFF
Heat Setpoint in Effect xx.x °F HSP_EFF
Effective Demand Temp xxx.x °F TEMP_EFF
Space Cooling Demand xx.x ΔF COOL_DMD
Cooling Demand Trend xx.x CLDTREND
Heating Space Demand xx.x ΔF HEAT_DMD
Heat Space Demand Trend xx.x HTDTREND
TESTMODE
Economizer Position Test 0 to 100 % S_DAMPER Writable
Compressor Bump A1 Test On/Off S_BMP A1 Writable
Rht Dischg Valve Rly Tst On/Off S_RDV_A Writable
Reheat Liq Valv Rly Test On/Off S_RL V_A Writable
Cooling Liq Valv Test On/Off S_CLV_A Writable
Crankcase Heater 1 test On/Off S_CCHR1 Writable
Alarm Output Relay Test On/Off S_ALARM Writable
Power Exhaust 1 T est On/Off S_PE_1 Writable
Power Exhaust 2 T est On/Off S_PE_2 Writable
2Position/ERV Relay Test On/Off S_ERV2P Writable
Indoor Fan Speed Test 0 t o 100 % S_IDFSPD Writable
IDF Manual Transition Yes/No S_IDFTRN Writable
Cooling W/Comp.A1 Test On/Off S_COOLA1 Writable
Cooling W/Comp.ALD Test On/Off S_COLALD Writable
ODF Speed Relay Test On/Off S_OFRSPD Writable
Humidimizer Level Test 0=Off,
1=Subcool,
2=Reheat
S_HMZLEV Writable
Heating Stage 1 Test On/Off S_HEAT1 Writable
Heating Stage 2 Test On/Off S_HEAT2 Writable
AUTO INDEPENDENT TEST Yes/No AUTOINDP Writable
RUN AUTO COOLING TEST Yes/No AUTOCOOL Writable
RUN AUTO HEATING TEST Ye s/No AUTOHEAT Writable
RUN AUTO SYSTEM TEST Yes/No AUTOSYS Writable
IDF_DIAG
IDF Commanded RPM 0 to 3000 RPM FSPD_RPM
Commanded IDF Speed 0 to 100 % FANSPEED
Request ed IDF Speed 0 to 100 % RQFANSPD
IDF Vent Speed --- RPM 0 to 3000 RPM RPM_VENT
IDF Heat Speed --- RPM 0 to 3000 RPM RPM_HEAT
IDF Free Cool Speed --- RPM 0 to 3000 RPM RPM_F CL
IDF Low Cool Speed--- RPM 0 to 3000 RPM RPM_LCL
IDF High Cool Speed---RPM 0 t o 3000 RPM RPM_HCL
IDF Maximum Fan Speed 0 to 100 % SPEEDMAX