7 - POSITIONING AND INSTALLATION
Air ducts connections
For units with vertical air ow, the ducts must be connected to the
pro les from underneath the roofcurb.
In order to carry out the air ducts follow the recommendations in
the paragraph 9.4 “Air ducts connections”.
A
E
D
C
A
A
A
F
A
B
A
A
153mm
A
Dimensions (mm) ABCDE F
Standard
roofcurb
100 to 120 51 1699 547 612 547 1699 (*)
130 to 170 51 2005 547 612 547 2005 (*)
180 to 220 51 2200 547 612 547 2200 (*)
250 to 280 51 2596 547 612 547 2596 (*)
Burner roofcurb
Dimensions (mm) AB CDEFGH I J
Burner
roofcurb
100 to
120
PCH080 50 1698 546 568 95 418 220 264 1522 164
PCH130 50 1698 546 171 95 943 92 264 1522 164
130 to 170 50 2004 546 171 95 943 92 264 1827 164
180 to 220 50 2200 546 171 95 943 92 264 2022 164
250 to 280 50 2597 546 171 95 943 92 264 2419 164
Standard roofcurb
G
E
D
C
F
A
A
B
A
I
H
J
A
Side view after installation on roof (position C):
Standard roofcurb
Burner roofcurb
β
= maximum slope
The thickness of the sheet metal pro les to connect the discharge
and/or return ducts to the roofcurb are shown in the following
tables:
Note: If the unit incorporates a hot water coil (optional), the length
of the supply duct is reduced by 153 mm.
β
= maximum slope
Important: Check that the roofcurb height is su cient to respect
the minimum sealing height required according to local regulations
(example: 150 mm minimum sealing height in France according
to DTU). To do this, check that the “D” dimension of the roofcurb
exceeds the thickness of the cladding plus the insulation plus the
minimum sealing distance required.
150mm min.
50FC unit
Steel panJoist
Roofcurb
Sealing
upsweep
D
Insulation
Dimensions (mm)
A B C DEF
β
Burner
roofcurb
100 to 120 1259 1121 109 1150 33 855 2,3º (4,0%)
130 to
170
PCH130 1259 1121 109 1150 33 855 2,0º (3,5%)
PCH160 1259 1121 109 1150 33 814 2,0º (3,5%)
180 a 220 1259 1121 109 1150 33 814 1,6º (2,8%)
250 to 280 1259 1121 109 1150 33 814 1,3º (2,3%)
Dimensions (mm)
ABCDE
β
Standard
roofcurb
100 to 120 538 400 133 405 33 2,3º (4,0%)
130 to 220 538 400 133 405 33 2,0º (3,5%)
250 to 280 538 400 133 405 33 1,3º (2,3%)
A
C
B
D
E
β
B
E
F
A
C
D
β