12 - COMPONENTS MANAGEMENT
Air renewal
Units with mixing air probe
Band
32ºC
30ºC28ºC26ºC24ºC22ºC
HEATING mode
14ºC
15ºC
16ºC
18ºC
20ºC
22ºC
0%
opening
100%
opening
where:
Minimum outlet air temperature = 30°C
Minimum return air temperature = 15°C
Return air setpoint temperature = 22°C
Damper control band = 2°C
supply T
ret.T
Units with mixing air probe + quality probe
Band
26ºC
24ºC22ºC20ºC18ºC16ºC
COOLING mode
24ºC
26ºC
28ºC
30ºC
31ºC
32ºC
100%
opening
0%
opening
where:
Minimum supply temperature = 20°C
Minimum return temperature = 31°C
Return setpoint temperature = 24°C
Damper control band = 2°C
supply T
ret.T
Overpressure control