17 - CONNECTING THE UNIT TO A BMS SUPERVISION NETWORK
17.1. Enabling supervision
          

G. GENCONFIG
17.2. Confi guration of the supervision network

J. BMSCONF 



U36a
Type of protocol
for supervision
network
Carel

RS485 serial card



KONNEX serial card (Con guration by the Integrator)



BACNET MSTP RS485 card (Con guration by the Integrator)



BACNET ETHERNET PCOWEB card (Con guration by the Integrator)



ETHERNET PCOWEB card



LONWORKS FTT serial card



U36b
Unit address
for supervision
network : 001
Baud rate : 19200
Stop bit No : 2
Parity type : No
CU14
Supervision Y
Summer fcooling Y
Winter fheating N
Winter fcooling Y
Air refreshing Y
100% outdoor air N
17.3. Failure of BMS communication
          



         

 
 
 
U36c
Enable BMS communicat.
fault detection: Y
Time for fault: 15 m
Var.digital BMS fault
detection n. 174: Y
BMS commun. fault:Y

           

U40a
VALUES WITHOUT BMS
Temp. control
setpoint
Summer 26.0ßC
Winter 21.0ßC
U40b
VALUES WITHOUT BMS
Unit off/on
ON
U40d
VALUES WITHOUT BMS
DISCONNECTING
No. compressor stages
to disconnect: 0
No. el.heaters stages
to disconnect: 0
U40e
VALUES WITHOUT BMS
Start type
'ON-OFF schedule'
U40c
VALUES WITHOUT BMS
Winter/Summer select.
'autimatic' by ind.T.
SUMMER
U40f
VALUES WITHOUT BMS
Program select.
Daily start
M:1 T:1 W:1 T:1 F:1
S:1 Su: -Sun-(0=off)
U40f
VALUES WITHOUT BMS
SCHEDULE PROGR. N.1
Slot 1>06:30 to 11:00
Slot 2>11:30 to 13:30
Slot 3>15:00 to 19:00