101
MODE — CONFIGURATION (cont)
ITEM EXPANS I O N RANGE UNITS DEFAULT
CCN TABLE/
Sub--- TABLE
CCN POINT ENTRY
AIR.Q Air Quality Config. IAQ_CFG
IA.CF IAQ Analog Input Config 0=No IAQ
1=DCV
2=Override IAQ
3=Ctrl Min Pos
0: no FIOP
1: FIOP
IAQANCFG
IA.FN IAQ Analog Fan Config 0=Never
1=Occupied
2=Always
0 IAQANFAN
II.CF IAQ Switch Input Config 0=No IAQ
1=DCV N/O
2=DCV N/C
3=Override N/O
4=Override N/C
0 IAQINCFG
II.FN IAQ Switch Fan Config 0=Never
1=Occupied
2=Always
0 IAQINFAN
AQ.MN E cono Min IAQ Position 0 to 100 % 10
0: FIOP EnergyX
IAQMINP
OVR.P IAQ Override Position 0 to 100 % 100 IAQOVPOS
OA.CF OAQ Analog Input Config 0=No OAQ
1=DCV
2=Lockout OAQ
0 OAQANCFG
OAQ.L OAQ Lockout Limit 0 to 5000 600 OAQLOCK
AQD.L AQ Differential Low 0 to 5000 100 DAQ_LOW
AQD.H AQ Differential High 0 to 5000 700 DAQ_HIGH
DF.ON FanOnAQDifferential 0 to 5000 600 DAQFNON
DF.OF Fan Off AQ Differential 0 to 5000 200 DAQFNOFF
I.4M IAQ Sens or V al u e at 4mA 0 t o 5000 0 IAQ_4MA
I.20M IAQ Sens or V al u e at 20mA 0 t o 5000 2000 IAQ_20MA
O.4M OAQ Sens or V alue at 4mA 0 to 5000 0 OAQ_4MA
O.20M OAQ Sen s or Val ue at 20mA 0 to 5000 2000 OAQ_20MA
H.4M RH Sensor V alue at 4mA 0to50 % 0 RH_4MA
H.20M RH Sens or V alu e at 20mA 60 to 100 % 100 RH_20MA
OAU Outside Air Unit Config OAU_CFG
OA.TY Outdoor Ai r Uni t Type 0=No OAU
1=ERV Module
2=Economizer
3=Pwr Exhaust
4=OA Monitor
5=100% OA Unit
6=EXv1 ERV
0: no FIOP
1: FIOP EnergyX
OAU_TYPE
OA.FC Outside Air Fan Curve 0 to 999 1: 04
2: 05--- 06
3: 07
4: 08--- 12
5: 14
6: 17--- 20
7: 24--- 28
OAFANCRV
PE.FC Exhaust Air Fan Curve 0 to 999 1: 04, 1ph, and econ
2: 04, 3ph, and econ
3: 04, 1ph, and no econ
4: 04, 3ph, and no econ
5: 05--- 06 1ph
6: 05--- 06 3ph
7: 07
8: 08--- 12
9: 14
10: 17--- 20 and econ
11: 17--- 20 and no econ
12: 24--- 28
PEFANCRV
U.RUN OAU Unoccup ied Operation No/Y es NO UNOCCRUN
OAU.F Shut Down on Fan Failure No/Yes Yes FATALOAU
M.WHL Modul atin g Wh eel Ins tall No/Yes NO MODWHEEL
OA.MN Minimum Outside Air CFM 0 to 32000 CFM 375: 04
800: 05--- 06
1000: 07
2500: 08--- 12
3000: 14
4000: 17--- 20
5000: 24--- 28
MINOACFM
DCV.M Min DCV Outside Air CFM 0 to 32000 CFM 100: 04
250: 05--- 06
600: 07
1000: 08--- 12
1500: 14--- 24
2000: 24--- 28
MINDCVSP
PEX.C Power Exhaust Control 0=Offset CFM
1=BP
0 PEX_CTL
PE.OF Power Exhaust CFM Offset --- 17000 to 17000 CFM --- 2 0 0 EXOFFSET
BP.SP Building Pressure Setpnt --- 0.25 to 0.25 in H2O 0.05 OAU_BPSP
OA.TM Outside Air Tempering Disable/Enable Disable OATEMPER
TM.LO OA Tempring Lockou t Temp 0to80 _F 60 OATMPLOC
ComfortLINK v1.X