83
APPENDIX A — LOCAL DISPLAY AND CCN TABLES
MODE — CONFIGURATION (cont)
ITEM EXPANSIO N RANGE UNITS DEFAULT
CCN TABLE/
S u b --- T A B L E
CCN POINT
PAGE
NO.
OAU Outside Air Unit Config OAU_CFG
OA.TY Ou tdoor Ai r Un it Type 0=No OAU
1=ERV Module
2=Economizer
3=Pwr Exhaust
4=OA Monitor
5=100% OA Unit
6=EXv1 ERV
0: no FIOP
1: FIOP EnergyX
OAU_TYPE 34
OA.FC Outside Air Fan Curve 0 to 999 1: 04
2: 05--- 06
3: 07
4: 08--- 12
5: 14
6: 17--- 20
7: 24--- 28
OAFANCRV
PE.FC Exhaust Air Fan Curve 0 to 999 1: 04, 1ph, and econ
2: 04, 3ph, and econ
3: 04, 1ph, and no econ
4: 04, 3ph, and no econ
5: 05--- 06 1ph
6: 05--- 06 3ph
7: 07
8: 08--- 12
9: 14
10: 17--- 20 and econ
11: 17--- 20 and no econ
12: 24--- 28
PEFANCRV
U.RUN OAU Unoccupied
Operation
No/Yes NO UNOCCRUN
OAU.F Shut Down on Fan Failure No/Yes Yes FATALOAU
M.WHL M odu l atin g Wheel In s tall No/Yes NO MODWHEEL
OA.MN Minimum Outside Air CFM 0 to 32000 CFM 375: 04
800: 05--- 06
1000: 07
2500: 08--- 12
3000: 14
4000: 17--- 20
5000: 24--- 28
MINOACFM
DCV.M Min DCV Outside Air CFM 0 to 32000 CFM 100: 04
250: 05--- 06
600: 07
1000: 08--- 12
1500: 14--- 24
2000: 24--- 28
MINDCVSP
PEX.C Power Exhaust Control 0=Offset CFM
1=BP
0 PEX_CTL
PE.OF Power Exhaust CFM Offset --- 17000 t o 17000 CFM --- 2 0 0 EXOFFSET
BP.SP Building Pressure Setpnt --- 0.25 to 0.25 in H2O 0.05 OAU_BPSP
OA.TM Outside Air Tempering Disable/Enable Disable OATEMPER
TM.LO OA Tempring Lockout Temp 0to80 _F 60 OATMPLOC
TM.SP OA Tempring SA T Setpoint 35 to 80 _F 55 OA TMPSPT
OAC.K Outside Air CFM k Factor 0.8 to 1.2 1 OACFM_K
EXC.K Exhaust Air CFM k Factor 0.8 to 1.2 1 EXCFM_K
OAFB OAU Fan Boost Enab l e No/Y es No EFB_ENBL
ALM.O Alarm Relay Config. ALM _CFG 17
A.SPC SPT/SPRH Sensor Failure No/Y es Yes SPACE_AL 31
A.SRT SAT/RAT Sensor Failure No/Yes Yes SA TRA TAL
A.OAT OAT Th ermistor Failure No/Yes Yes OAT_AL
A.CMP Compress or Failu re No/Yes Yes COMP_AL
A.CKT Refrig Circuit Failu re No/Yes Yes CKT_AL
A.SSP SSP Transducer Failure No/Y es Yes SSP_AL
A.SCT SCT Thermistor Failu re No/Y es Yes SCT_AL
A.FAN Ind oor Fan F ai lu r e No/Y es Yes FAN_AL
A.FIL Dirty Filter No/Yes Ye s FILT_AL
A.TST Thermostat Failure No/Yes Yes TSTAT_AL
A.ECO Econ om izer F ail u re No/Yes Yes ECON_AL
A.OAU Outside Air unit Alarms No/Yes Yes OAU_AL
PID PI D Con fi g u rati on s PID_CFG 31
EC.P Econ omi zer PID --- kP 0.00 to 99.90 2.5 ECONO_P
EC.I Econ omi zer PID --- kI 0.00 to 99.90 0.12 ECONO_I
EC.D Ec on omi zer PID --- kD 0.00 to 99.90 1 ECONO_D
EC.DT Econ om iz er PID --- rate 10.00 to 180.00 secs 15 ECONO_DT
EC.DB Ec on omi zer PID Deadban d 0to25 % 3 ECONBAND
LK.P Linkage Staging PID -- - kP 0.00 to 99.90 10 LINK_P
LK.I Linkage Staging PID --- kI 0.00 to 99.90 5 LINK_I
LK.D Linkage Staging PID --- kD 0.00 to 99.90 5 LINK_D
LK.DT Linkage Staging PID - -- rate 10.00 to 180.00 secs 30 LINK_DT
ComfortLINK v1.X