EasyManua.ls Logo

Carrier 50HJ012 User Manual

Carrier 50HJ012
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500015-01 Printed in U.S.A. Form 50HJ-32SI Pg 1 9-05 Replaces: 50HJ-28SI
Book 1 4
Tab 1b 6b
Installation, Start-Up and
Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS ......................1
INSTALLATION ................................ 1-46
Step 1 Provide Unit Support ...................1
ROOF CURB
SLAB MOUNT
ALTERNATE UNIT SUPPORT
Step 2 Field Fabricate Ductwork ...............2
Step 3 Install Condensate Drain Line
and External Trap ..............................2
Step 4 Rig and Place Unit .....................4
POSITIONING
Step 5 Make Electrical Connections ........... 7
FIELD POWER SUPPLY
FIELD CONTROL WIRING
HEAT ANTICIPATOR SETTINGS
Step 6 Adjust Factory-Installed
Options .......................................12
HUMIDI-MIZER™ ADAPTIVE DEHUMIDIFICA-
TION SYSTEM
DISCONNECT SWITCH
CONVENIENCE OUTLET
NOVAR CONTROLS
MANUAL OUTDOOR-AIR DAMPER
PREMIERLINK™ CONTROL
OPTIONAL ECONOMI$ER IV AND ECONOMI$ER2
ECONOMI$ER IV STANDARD SENSORS
ECONOMI$ER IV CONTROL MODES
Step 7 Adjust Evaporator-Fan Speed .........25
PRE-START-UP ..................................43
START-UP .................................... 43-47
SERVICE ..................................... 47-51
TROUBLESHOOTING......................... 52-55
INDEX ...........................................56
START-UP CHECKLIST ........................CL-1
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precau-
tions in the literature, tags and labels attached to the unit, and
other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguisher available for all brazing operations.
INSTALLATION
Unit is shipped in the vertical configuration. To convert to
horizontal configuration, remove side duct opening covers. Us-
ing the same screws, install covers on vertical duct openings
with the insulation-side down. Seals around duct openings
must be tight. See Fig. 1.
Step 1 Provide Unit Support
ROOF CURB Assemble and install accessory roof curb in
accordance with instructions shipped with curb. See Fig. 2.
Install insulation, cant strips, roofing felt, and counter flashing
as shown. Ductwork must be attached to curb. If electric or
control power is to be routed through the basepan, attach the
accessory thru-the-bottom service connections to the basepan
in accordance with the accessory installation instructions. Con-
nections must be installed before unit is set on roof curb.
Curb should be level. This is necessary for unit drain to
function properly. Unit leveling tolerances are shown in Fig. 3.
Refer to Accessory Roof Curb Installation Instructions for
additional information as required.
SLAB MOUNT (Horizontal Units Only) Provide a level
concrete slab that extends a minimum of 6 in. beyond unit
cabinet. Install a gravel apron in front of condenser coil air inlet
to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.
ALTERNATE UNIT SUPPORT When the curb or adapter
cannot be used, support unit with sleeper rails using unit curb
or adapter support area. If sleepers cannot be used, support the
long sides of the unit with a minimum of 3 equally spaced
4-in. x 4-in. pads on each side.
Ensure voltage listed on unit data plate agrees with electri-
cal supply provided for the unit.
Before performing service or maintenance operations on
unit, turn off main power switch to unit and install lockout
tag. Electrical shock could cause personal injury.
IMPORTANT: The gasketing of the unit to the roof curb
is critical for a watertight seal. Install gasket supplied
with the roof curb as shown in Fig. 2. Improperly
applied gasket can also result in air leaks and poor unit
performance.
50HJ008-014
Single-Package Rooftop
Electric Cooling Units

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the Carrier 50HJ012 and is the answer not in the manual?

Carrier 50HJ012 Specifications

General IconGeneral
BrandCarrier
Model50HJ012
CategoryAir Conditioner
LanguageEnglish

Summary

SAFETY CONSIDERATIONS

Installation, Start-Up and Service Instructions

Overview of installation, start-up, and service procedures for the unit.

INSTALLATION

Step 1 - Provide Unit Support

Instructions for providing appropriate support for unit installation, including roof curbs and slab mounts.

Step 3 - Install Condensate Drain Line and External Trap

Details on installing the condensate drain line and an external trap for proper drainage.

Step 4 - Rig and Place Unit

Procedures for rigging and safely placing the unit onto its installed support structure.

Step 5 - Make Electrical Connections

Step-by-step instructions for making all necessary electrical connections, including power and control wiring.

Step 6 - Adjust Factory-Installed Options

Guidance on adjusting factory-installed options such as Humidi-MiZer™ and disconnect switches.

Unit Leveling Tolerances

Rigging Details

Visual guide and notes on rigging procedures, including lifting hole locations and weight information.

Power Wiring Connections

Field Power Supply

Instructions for field power supply connections, emphasizing safety and NEC compliance.

Electrical Data

Low-Voltage Connections

Fig. 9A - Low-Voltage Connections (Standard Controls)

Wiring diagram for low-voltage connections on units with standard controls, showing thermostat wiring.

Fig. 9B - Low Voltage Connections (Units with PremierLink™ Controls)

Wiring diagram for low-voltage connections on units with PremierLink™ controls.

Humidi-MiZer™ Adaptive Dehumidification System

Subcooling Mode

Detailed explanation of the subcooling mode operation for the Humidi-MiZer system.

Hot Gas Reheat Mode

Explanation of the hot gas reheat mode for humidity control with the Humidi-MiZer system.

Humidi-MiZer Wiring Diagrams

Fig. 14 - Typical Rooftop Unit with Humidi-MiZer Adaptive Dehumidification System Wiring with Thermidistat Device

Wiring diagram for the Humidi-MiZer system when used with a Thermidistat device.

Manual Outdoor-Air Damper

PremierLink™ Control

PremierLink Controller Compatibility

Information on the PremierLink controller's compatibility with Carrier Comfort Network (CCN) devices and diagnostic tools.

PremierLink Controller

Fig. 19 - PremierLink Controller

Diagram of the PremierLink controller, showing sensor inputs and outputs.

PremierLink Sensor Usage

Table 5 - PremierLink Sensor Usage

Table detailing the required sensors for different PremierLink control applications and modes.

Enthalpy Sensors and Control

EconoMi$er IV Wiring

EconoMi$er2 Wiring

EconoMi$er IV Control Modes

EconoMi$er IV Controller Potentiometer and LED Locations

Demand Controlled Ventilation (DCV)

Evaporator-Fan Speed Adjustment

PRE-START-UP

Pre-Start-Up Inspections

Checklist of pre-start-up inspections to ensure the unit is ready for operation and safe.

START-UP

Unit Preparation

Steps for preparing the unit for start-up, including filter checks and electrical connections.

Compressor Rotation

Procedure to check and correct compressor rotation direction to prevent damage.

Cooling

COOLING, UNITS WITH ECONOMI$ER2, PREMIERLINKTM CONTROL AND A THERMOSTAT

Cooling operation for units with EconoMi$er2 and PremierLink control using a thermostat.

Economizer Control Logic

SERVICE

Humidi-MiZer Adaptive Dehumidification System Sequence of Operation and System Response

Refrigerant Charge

HUMIDI-MIZER™ SYSTEM CHARGING

Instructions for charging systems equipped with the Humidi-MiZer adaptive dehumidification system.

Cooling Charging Charts

Fig. 60 - Cooling Charging Chart, 50HJ008 With Optional Humidi-MiZer™™ Adaptive Dehumidification System

Charging chart for 50HJ008 with Humidi-MiZer, showing liquid pressure vs. temperature.

Fig. 61 - Cooling Charging Chart, 50HJ009,012 With Optional Humidi-MiZer Adaptive Dehumidification System

Charging chart for 50HJ009/012 with Humidi-MiZer, showing liquid pressure vs. temperature.

Fig. 62 - Cooling Charging Chart, 50HJ014 With Optional Humidi-MiZer Adaptive Dehumidification System

Charging chart for 50HJ014 with Humidi-MiZer, showing liquid pressure vs. temperature.

TROUBLESHOOTING

Table 31 - Humidi-MiZer™™ Adaptive Dehumidification System Subcooling Mode Service Analysis

Service analysis for subcooling mode issues in the Humidi-MiZer system, listing problems, causes, and remedies.

Table 32 - Humidi-MiZer Adaptive Dehumidification System Hot Gas Reheat Mode Service Analysis

Service analysis for hot gas reheat mode issues in the Humidi-MiZer system, listing problems, causes, and remedies.

Cooling Troubleshooting

Table 33 - Cooling Troubleshooting

Table providing common cooling problems, their causes, and recommended remedies.

EconoMi$er IV Troubleshooting

Table 34 - EconoMi$er IV Input/Output Logic

Table outlining the input/output logic for the EconoMi$er IV system and its various modes.

EconoMi$er IV Functional View

SERVICE TRAINING

START-UP CHECKLIST

II. PRE-START-UP

Checklist for pre-start-up verification, ensuring all installation and safety steps are completed.

III. START-UP ELECTRICAL

Section for recording electrical measurements during start-up, including voltage and amperage.

Related product manuals