EasyManua.ls Logo

Carrier 50HJ012 - Fan Rpm at Motor Pulley Setting*; Standard Motor;Drive; Fan Rpm at Motor Pulley Setting*; High-Static Motor;Drive; Evaporator-Fan Motor Data - Standard Motor

Carrier 50HJ012
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
27
Table 10 Fan Rpm at Motor Pulley Setting*; Standard Motor/Drive
*Approximate fan rpm shown.
Table 11 Fan Rpm at Motor Pulley Setting*; High-Static Motor/Drive
*Approximate fan rpm shown.
Table 12 Evaporator-Fan Motor Data Standard Motor
LEGEND
BHP Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of
the motors can be utilized with confidence. Using the fan motors up to the ratings shown in this table will
not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
UNIT
50HJ
MOTOR PULLEY TURNS OPEN
0
1
/
2
11
1
/
2
22
1
/
2
33
1
/
2
44
1
/
2
55
1
/
2
6
008,009 1085 1060 1035 1010 985 960 935 910 890 865 840
012 1080 1060 1035 1015 990 970 950 925 905 880 860
014 1130 1112 1087 1062 1037 1012 987 962 987 912 887 862 830
UNIT
50HJ
MOTOR PULLEY TURNS OPEN
0
1
/
2
11
1
/
2
22
1
/
2
33
1
/
2
44
1
/
2
55
1
/
2
6
008 1080 1025 1007 988 970 952 933 915 897 878 860
009 1080 1025 1007 988 970 952 933 915 897 878 860
012 1130 1112 1087 1062 1037 1012 987 962 937 912 887 862 830
UNIT
50HJ
UNIT
PHASE
MAXIMUM
CONTINUOUS BHP*
MAXIMUM
OPERATING WATTS*
UNIT VOLTAGE
MAXIMUM
AMP DRAW
008,009 Three 2.90 2615
208/230 8.6
460 3.9
575 3.9
012 Three 3.70 3775
208/230 12.2
460 5.5
575 5.5
014 Three 5.25 4400
208/230 17.3
460 8.5
575 8.5

Table of Contents