46
LEGEND
* Table 12 illustrates the complete hierarchy. Your menu parameters
may be different depending on your configuration. For example if you
do not have a DCV (CO
2
) sensor, then none of the DCV parameters
appear.
† When values are displayed, pressing and holding the or button
causes the display to automatically increment.
** N/A = Not Applicable.
†† ERV Operation: When in cooling mode AND the conditions are NOT
OK for economizing - the ERV terminal will be energized. In the Heat-
ing mode, the ERV terminal will be energized when the OA is below
the ERV OAT set point in the set point menu.
*** After 10 minutes without a command or mode change, the controller
will change to normal operation.
NOTES:
1. STATUS —> OCCUPIED — The factory-standard Occupancy
signal originates with a thermostat or other controller call for
indoor fan operation at CTB terminal G. This signal passes
through the Central Terminal Board’s OCCUPANCY jumper to the
ECONO connector and to the W7220’s OCC input terminal. An
external timeclock or relay is required to implement an
Occupancy schedule on the economizer damper position.
2. STATUS —> MA TEMP, SETPOINTS —> MAT SET — The W7220
menu parameters and labels include designations MA, MAT and
Mixed Air for the economizer cooling control sensor. On these
rooftop units, the economizer control sensor is located downstream
of the evaporator/indoor coil in the supply fan section where this
sensor is designated as Supply Air Temperature (SAT) sensor.
3. SETPOINTS —> DRYBLB SET — This point is not displayed if a
Return Air (differential) temperature sensor or an Outdoor Air
enthalpy sensor is connected.
4. SYSTEM SETUP parameters must be configured as noted for 2-
Speed unit operation:
EQUIPMENT = CONV
AUX2 I = W
FAN SPEED = 2SPEED
For damper minimum position settings and checkout menu read-
ings, see Table 13. For dry bulb operation with or without DCV,
see Tables 14 and 15. For enthalpy operation with or without
DCV, see Tables 16 and 17.
*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2–O after the delay if the call for Y–I and
Y2–I have not been satisfied.
ALARMS
(cont)
ACT UNDER V N/A N/A
ACTUATOR VOLTAGE LOW
Voltage received by actuator is above expected range.
ACT OVER V N/A N/A
ACTUATOR VOLTAGE HIGH
Voltage received by actuator is below expected range.
ACT STALLED N/A N/A
ACTUATOR STALLED
Actuator stopped before achieving commanded position.
Table 12 — W7220 Menu Structure* (cont)
MENU PARAMETER
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND
INCREMENT
EXPANDED PARAMETER NAME
Notes
CLO Compressor Lockout
ERV Energy Recovery Ventilator
LCD Liquid Crystal Display
MA Mixed Air
MAT Mixed Air Temperature
N/A Not Applicable
OA Outdoor Air
OAT Outdoor Air Temperature
OCC Occupied
RA Return Air
RAT Return Air Temperature
RTU Rooftop Unit
SYS System
Table 13 — Damper Minimum Position Settings and Readings on Checkout Menu
DEMAND CONTROLLED
VENTILATION
(CO
2
SENSOR)
FAN SPEED SETPOINTS CHECKOUT
NO
1
MIN POS VMAX–HS
N/A N/A
YES
VENT MIN VMAX–HS
VENT MAX VMAX–HS
Table 14 — Dry Bulb Operation Without DCV (CO
2
Sensor) — 1 Speed Fan
DEMAND
CONTROLLED
VENTILATION (DCV)
OUTSIDE AIR
GOOD TO
ECONOMIZE
Y1-I Y2-I FAN SPEED Y1-O Y2-O OCCUPIED UNOCCUPIED
NONE
No
Off Off High 0-v/Off 0-v/Off MIN POS Closed
On Off High 24-v/On 0-v/Off MIN POS Closed
On On High 24-v/On 24-v/On MIN POS Closed
Yes
Off Off High 0-v/Off 0-v/Off MIN POS Closed
On Off High 0-v/Off 0-v/Off
MIN POS to
Full-Open
Closed to
Full-Open
On On High 24-v/On 0-v/Off*
MIN POS to
Full-Open
Closed to
Full-Open