27
12 - SAFETY ELEMENTS
Remote alarm (optional)
"50FC" control allows the management of a relay for remote
alarm signaling.
The output for the general alarm signal is not compatible with
the heat recovery coil (optional).
In this case, upon request, it would be possible to have a general
alarm output in an input/output expansion module (see the
"50FC" control manual).
Smoke detecting probe
Clogged lter detector (optional)
A di erential pressure switch is a device used for detecting the
lter clogging level.
This pressure switch is installed in the electric cabinet of the
indoor module at the factory.
Filter classi cation Pressure drop (Pa)
G4 150
F7 250
Note: all lter frames are labelled with a sticker that indicates
their classi cation.
The probe is placed next to the supply fans.
Smoke
detecting
station
The pressure measurement is done using
two intakes located within the air ow, making
a comparison between the air pressure at the
inlet to the lter (positive) and the pressure
at the outlet, on the other side of the coil
(negative).
Note: With a mixing box (optional), the lters
are located inside it, and the intake at the
inlet to the lter must pass through a bushing inside the box.
The electronic control allows the settings selection for the
clogged lter alarm: only indication (by default) or unit stoppage.
Manual reset.
The pressure switch set value for alarm signaling is con gured
in the factory, depending on the lters selected for the unit,
according to the following criterion (Standard EN 13053):
Unit lter: the set value is the pressure drop for the lter
classi cation, according to the attached table.
Serial lters: the set value is the pressure drop of the highest
e ciency lter + half of the pressure drop of the other lter,
according to the attached table.
Clogged
lter
detector
Smoke detector (optional)
This smoke-detecting station, in accordance with the NF S 61-
961 standard, uses a LED to indicate the installation status, If
the probe detects the presence of smoke in the installation, it
stops the operation of the unit and gives the order to open or
close the outdoor damper (con gured by parameter).
To ensure compliance with the French regulations on Fire
safety (ERP), it’s possible to con gure the opening of the fresh
air damper and the exhaust air damper to 100% (return air
damper closed).
The station is installed in the factory in the electrical cabinet
of the indoor module. To reset the station, it is necessary to
disassemble the protection box.