Page #14 background image
UNIT
SINGLE-PHASE
COMPRESSORS
are
equipped
with
a
Compressor
Start
Thermistor
(PTC
device).
When
supply
voltage
is
within
10%
limit
and
compressor
does
not
start,
check
the
start
thermistor
with
an
ohmmeter.
Checking
Start
Thermistor
1.
Shut
off
all
power
to
unit
and
wait
10
minutes
for
thermistor
to
cool
to
ambient
temperature.
2.
Remove
thermistor
from
circuit.
3.
Measure
resistance
of
thermistor
with
ohmmeter.
Nor¬
mal
resistance
readings
are
12.5
or
25
ohms
+
20%
at
75
F
ambient
temperature
depending
on
your
unit.
4.
I
f
ohmmeter
resistance
reading
is
not
within
±
20%,
the
thermistor
is
defective
and
must
be
replaced.
If
start
thermistor
is
good
and
compressor
does
not
start,
disconnect
the
thermistor
from
starting
circuit
and
give
compressor
a
temporary
capacitance
boost.
Run
compressor
for
10
minutes,
then
shut
off
and
allow
system
pressure
to
equalize.
Reconnect
start
thermistor
and
try
restarting
compressor
without
boost
capacitor.
If
after
two
attempts
the
compressor
does
not
start,
remove
thermistor
and
add
an
accessory
start
capacitor
and
relay.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier 50NQ and is the answer not in the manual?

Carrier 50NQ Specifications

General IconGeneral
BrandCarrier
Model50NQ
CategoryHeat Pump
LanguageEnglish

Related product manuals