d.
Make
sure
that
all
tools
and
miscellaneous
loose
parts
have
been
removed.
Unit
is
now
ready
for
initial
startup.
REFRIGERANT
LEAKS
Proceed
as
follows
to
repair
a
refrigerant
leak
and
to
charge
the
unit:
1.
Locate
leak
and
ensure
that
refrigerant
system
pres¬
sure
has
been
relieved.
2.
Repair
leak
following
accepted
practices.
NOTE:
Install
a
filter-drier
whenever
the
system
has
been
opened
for
repair.
3.
Add
a
small
charge
of
R-22
refrigerant
vapor
to
system
and
leak-test
unit.
4.
Evacuate
refrigerant
system
if
additional
leaks
are
not
found.
5.
Charge
unit
with
R-22
refrigerant,
using
a
volumetric-
charging
cylinder
or
accurate
scale.
Refer
to
unit
rating
plate
for
required
charge.
Be
sure
to
add
extra
refriger¬
ant
to
compensate
for
internal
volume
of
filter-drier.
START-UP
AND
ADJUSTMENTS
A
CAUTION
Complete
the
required
procedures
given
in
“Preparing
Unit
for
Start-up,”
page
7,
before
starting
the
unit.
Do
not
jumper
any
safety
devices
when
operating
the
unit.
Do
not
operate
unit
in
the
cooling
mode
when
the
out¬
door
temperature
is
below
55
F
(unless
accessory
low-
temperature
kit
is
installed).
Do
not
operate
unit
in
heating
mode
when
outdoor
tem¬
perature
is
above
60
F.
Do
not
rapid-cycle
the
compressor.
Allow
5
minutes
between
“on”
cycles
to
prevent
compressor
damage.
The
unit
compressor
is
equipped
with
a
crankcase
heater.
It
is
recommended
that
heater
be
energized
a
minimum
of
24
hours
before
starting
unit.
To
energize
heater
only,
set
ther¬
mostat
at
OFF
position;
turn
on
unit
main
power
at
discon¬
nect
switch.
TO
START
UNIT—Check
that
main
power
is
on
and
that
compressor
crankcase
heater
has
been
energized
for
at
least
24
hours.
1.
Check
that
heater
main
power
is
on
as
applicable.
2.
Set
selector
switch
at
OFF.
3.
Set
fan
switch
as
desired
(FAN)
(AUTO.).
4.
Set
thermostat
dial
at
the
desired
temperature.
5.
Set
selector
switch
at
HEAT
or
COOL.
Check
system
refrigerant
charge
as
described
in
“Checking
Charge”
section
below.
CHECKING
CHARGE—Factory
Charge
is
shown
on
unit
rating
plate
(See
Fig.
4).
A
CAUTION
Compressor
damage
may
occur
if
system
is
over¬
charged.
Adjust
charge
in
cooling
mode
by
following
procedure
shown
on
the
“superheat
charging
tables”
located
on
unit.
Check
charge
in
heating
by
following
procedure
shown
on
“heating
check
chart”
located
on
unit.
9