CL-3
MODE — CONFIGURATION (cont)
LEGEND
FIOP — Factory-Installed Option
ITEM EXPANSION RANGE DEFAULT ENTRY
CONFIGURATION (cont)
OFC (cont)
3.OFF Fan Lev3 Off Temperature 0 to 100 F no Humidi-MiZer FIOP:
55
Humidi-MiZer FIOP:
78 (20)
62 (24)
62 (28)
HMZR Humidimizer Config
REHT Humidimizer Equipped Yes/No No: no Humidi-MiZer
FIOP
Yes: Humidi-MiZer FIOP
R.DEC Reheat2 Stage Decr.
Time
0 to 999 secs 60
R.INC Reheat2 Stage Incr. Time 0 to 999 secs 300
RH.FN Reheat Fan Control Yes/No Yes
RF.LV Reheat2 ODF Fan On
Level
0 to 3 2
RF.ON Reheat2 ODF Fan On
Tem p
0 to 100 F 93 (20)
93 (24)
85 (28)
RF.OF Reheat2 ODF Fan Off
Tem p
0 to 100 F 83 (20)
88 (24)
80 (28)
RA.LO Reheat2 OAT Limit A 20 to 70 F 40
RA.LP Reheat2 SSP Lo Limit A 50 to 100 psig 80
RA.HP Reheat2 SSP Hi Limit A 50 to 100 psig 90
RB.LO Reheat2 OAT Limit B, C 20 to 70 F 50
RB.LP Reheat2 SSP Lo
Limit B, C
50 to 100 psig 80
RB.HP Reheat2 SSP Hi
Limit B, C
50 to 100 psig 90
HEAT Heating Configuration
HT.TY Type of Heat Installed 0 = No Heat
1 = Gas
2 = Electric
0 (50 series with no
electric heat)
1 (48 series)
2 (50 series with electric
heat)
N.HTR Number of Heat Stages 1 to 2 1 (48 series 1-phase,
50 series <15kW)
2 (48 series 3-phase,
50 series >=15kW)
MRT.H Heat Minimum On Time 60 to 999 sec 120
MOT.H Heat Minimum Off Time 60 to 999 sec 120
H.DEC Heat Stage Decrease
Rate
120 to 999 sec 300
H.INC Heat Stage Increase Rate 120 to 999 sec 450
FOD.E Fan-off Delay, Elect Heat 10 to 600 sec 30
FOD.G Fan-off Delay, Gas Heat 45 to 600 sec 45
HT.LO Heating Lockout Temp 40 to 125 dF 75
SAT.H SAT Heat Mode Sensing Enable/Disable Disable
SPT Space Temperature
Sensor
HT.PD SPT Heat Demand (+)
Level
0.5 to 5 ^F 1
HT.ND SPT Heat Demand (–)
Level
–5 to –0.5 ^F –1
H.LAG Heat Thermal Lag Factor 0 to 5 min 1
ECON Economizer Configuration
EC.EN Economizer Installed Yes/No No: no FIOP
Yes: FIOP
E.CTL Economizer Control Type 1=Digital, Position Feed-
back
2=Digital, Command
Feedback
3=Analog Control
1
EC.MN Econo Minimum Position 0 to 100 % 30
EC.MX Econo Cool Max Position 0 to 100 % 100
EH.LO Econo Cool Hi Temp Limit 40 to 100 dF 65
EL.LO Econo Cool Lo Temp
Limit
–30 to 50 dF 0
UEFC Unoccupied Free Cooling 0=Disabled
1=Entire Unoccupied
Period
2=PreOccupancy Time
2